|
|
|
|
|
|
|
|
Navigating the Path to Compliance with the
New Edition of UL 1950
Gary H. Wiseman and Mario H. Gomez
For manufacturers of computers, fax
machines, telephones, modems, and other information
technology equipment, April 1, 2000, will
be more than just another April Fools' Day.
This
day will mark an important step forward for
the computing and communications industry
as the Underwriters Laboratories Inc. (UL)
1950 3rd ed., "Safety of Information Technology
Equipment, Including Electrical Business Equipment,"
takes full effect. This article focuses specifically
on the new elements of UL 1950 3rd ed. that
apply to equipment connected to telecommunications
networks, explains the requirements of the
standard, and provides some options for manufacturers
who need to comply with the requirements.
A Brief History of Standards Integration
The first version of UL 1950 was created
to harmonize UL 478 and UL 114 into one safety
standard. During the 1980s, UL 478 was the
standard for electronic data processing equipment,
and UL 114 was the standard for office appliances
and business equipment. The development of
the PC and its widespread use in the business
environment created a new problem: some manufacturers
were submitting PCs to UL for listing under
UL 114, while others were submitting to UL
478. Hence, a new standard was developed that
for a short time was referred to as UL 478
5th ed.
At about the same time, similar harmonizing
efforts were under way in the international
standards community. During this period, IEC
380 applied to typical office equipment, and
IEC 435 applied to electronic data processing
equipment. These two standards were harmonized
into a new standard that became IEC 950. Recognizing
the many similarities between this standard
and UL's new standard (UL 478 5th ed.), UL
agreed to harmonize UL 478 5th ed. with IEC
950. The new harmonized standard became the
first edition of UL 1950. Canada also had
a similar situation with two different safety
standards being used for office equipment
and electronic data equipment. Thus, the Canadian
Standards Association (CSA) also developed
a standard based on IEC 950 called CSA 950,
which is now CSA standard C22.2 No. 950-95,
3rd. ed.
By the late 1980s, it became clear
that additional integration of standards would
be required to account for the convergence
of computing and communications equipment.
Desktop computers of this era routinely included
modems, often with built-in fax and telephony
capabilities. The compliance community was
faced with a difficult issue: should these
devices be considered computers and be covered
by UL 1950 or telephones that would be covered
by UL 1459, a standard for telephony equipment?
This type of issue was occurring so frequently
that UL proposed to merge the two standards.
In the end, a U.S. and Canadian working group
was formed to explore the integration of four
standards: UL 1950, CSA C22.2 No. 950, UL
1459, and CSA C22.2 No. 225 (the Canadian
equivalent of UL 1459). The new binational
standard that resulted from this effort in
1995 was CSA 950/UL 1950 3rd ed.
The broad scope of UL 1950 3rd ed.
encompasses equipment ranging from calculators
and cash registers to facsimile equipment,
modems, PBXs, and PCs. Because of the profound
changes embodied in UL 1950 3rd ed., UL developed
a phased implementation plan. Until April
1, 2000, manufacturers are allowed to seek
listing to earlier editions of UL 1950 or
UL 1459 and their Canadian equivalents. Beginning
April 1, 2000, however, all new information
technology equipment may only be listed to
UL 1950 3rd ed., and UL 1459 will in effect
cease to exist. Listings previously granted
under earlier versions of these standards
will remain valid until April 1, 2005. After
2005, however, such equipment still available
for sale must be reevaluated and listed to
UL 1950 3rd ed. because the prior listing
will no longer be valid. Therefore, it is
in a manufacturer's interest to seek listing
to UL 1950 3rd ed. for equipment intended
for a long market life.
Protection Philosophy Changes in UL 1950
3rd Ed.
When the binational working group considered
integrating UL 1459 into UL 1950, it adopted
an important philosophical change about protection
and safety of equipment connected to the telecommunications
network. The test requirements of UL 1459
were designed to ensure not only the safety
of the equipment but also the protection of
building wiring and coordination of protection
with the primary overvoltage protector typically
located outside the building or house. In
UL 1459, the safety and protection coordination
objectives were accomplished by subjecting
the equipment to three types of tests: a 600-V,
40-A test simulating power contact with a
high-voltage distribution power line; 600-V,
7-A and 600-V, 2.2-A tests simulating power
induction (induced voltage and current from
a distribution ground fault); and a 120-V,
25-A (or 240-V, 24-A) test simulating power
cross with ac mains voltage. In each case,
to ensure equipment safety, it was required
that the cheesecloth wrapped around the equipment
did not char. Building wiring protection was
also ensured by requiring that a wiring simulator
(often represented by a 1.6 A fuse) did not
open during the test.
Equipment manufacturers typically complied
with the UL 1459 overvoltage requirements
by using specially designed fuses or polymer
positive temperature coefficient (PTC) devices
for overcurrent protection. The fuses or PTC
devices served to interrupt the flow of current
before any part of the equipment burned and
charred the cheesecloth, and also before the
wiring simulator opened.
As UL 1950 3rd ed. began to take shape,
the binational working group decided that
protection of building wiring was outside
the scope of the standard; hence, the need
for coordinated protection by limiting current
would not be a requirement. In addition, computer
industry representatives stated that by using
certain construction techniques, computer
equipment connected to the telecommunications
network had demonstrated a good safety record
with respect to telephone line overvoltages.
Therefore, the working group decided that
information technology equipment manufacturers
should be allowed greater flexibility in deciding
how to meet the equipment safety objectives
relative to the tests prescribed in UL 1459.
This decision led to the creation of a fairly
complex-looking flowchart shown in the standard
as Figure 18b, "Overvoltage flowchart." This
flowchart is shown here in Figure 1.
 |
| Figure 1. UL 1950 3rd
ed. overvoltage flowchart (Figure 18b
within the UL document). |
Even though the chart looks fairly complicated,
the binational working group envisioned that
manufacturers would typically follow one of
the three vertical pathways to get from the
"Connects to outside cable" rectangle to the
"Acceptable" one. Starting from the right,
these paths are as follows:
1) A "performance" path comprising testing
the equipment to diamonds "Pass 1," "Pass
5," and "Pass 2, 3, 4."
2) A "construction" path comprising meeting
the requirements of diamonds "Min. 26 AWG
line cord," "Pass 6.3.3," and "Fire enclosure
and spacings."
3) A "construction using current limiting"
path comprising meeting the requirements of
diamonds "100 A2-seconds limiting,"
"1.3 A limiting," and "Fire enclosure."
The key requirements of these three paths
and a fourth option that may be adopted by
some manufacturers as they seek equipment
listing to UL 1950 3rd ed. will be described.
The performance path requires following
the decision diamonds on the far right side
of Figure 1. It involves testing the equipment
to essentially the same set of requirements
that are contained in UL 1459 and CSA C22.2
No. 225. These test requirements are described
in Annex NAC of UL 1950 3rd ed. and summarized
in Table I.
|
Test
|
Connection1
|
Test
Condition
|
Passing
Criteria2
|
|
1
|
M,
L, F
|
600
V, 40 A, 1.5 seconds
|
a,
b1, b2, c
|
|
2
|
M,
L, F
|
600
V, 7 A, 5 seconds
|
a,
c
|
|
3
|
M,
L, F
|
600
V, 2.2 A, 30
minutes or
until open circuitif open
circuit, test at 3 A
|
a,
c
|
|
3A
|
M,
L, F
|
600
V, I < 2.2 A, so no open circuit
to produce maximum heating, 30 minutes
|
a,
c
|
|
43
|
M,
L, F
|
V
< conduction
voltage, I < 2.2
A to produce maximum heating, 30 minutes
or until open circuit
|
a,
c
|
|
5
|
L
|
120
V, 25 A, 30 minutes or
until open circuit
|
a,
b1, c
|
1
Connection: M = differential mode (metallic)apply
voltage source across tip and ring; L
= common mode (longitudinal)apply
voltage source from tip to ground and
ring to ground; F = four wire test modeapply
voltage from pair 1 to pair 2.
2 Passing Criteria: a)
no charring of cheesecloth indicator;
b1) fuse or wiring simulator (Bussmann
MDL-2A fuse) does not interrupt; b2) I2t
< 100 A2-seconds; c) meet
dielectric withstand or leakage current
requirements after test.
3 To be done if voltage
limiter operated in test 3. |
|
Table I. Performance
path test requirements.
|
To meet the requirements of the performance
path, an OEM must ensure that the equipment
is "safe" per the overvoltage conditions that
have been traditionally agreed to by the telecommunications
industry. In addition, protection coordination
with building wiring and primary overvoltage
protectors is obtained because passing test
1 requires that the equipment limit fault
energy to less than 100 A2-seconds
under 600-V power contact conditions. We expect
that many traditional telephone equipment
manufacturers will follow this path because
the circuit protection solutions such as fuses
and PTC devices that they are currently using
to meet UL 1459 are likely to meet the UL
1950 3rd ed. requirements.
The construction path requires following
the three vertical diamonds in the center
of Figure 1. The construction requirements
were developed to provide an equivalent level
of equipment safety to the performance path,
though clearly not an equivalent performance
or design. There are three requirements to
meet in this path: supplying line cord, passing
an insulation strength test, and providing
an appropriate fire enclosure.
Supply minimum 26 AWG line cord. To
meet this requirement, the manufacturer must
either supply a telecommunications line cord
with 26 AWG wire or larger, or describe the
necessity of using such wire in the safety
instructions. An example of such a statement
is provided in Annex NAA: "CautionTo reduce
the risk of fire, use only No. 26 AWG or larger
telecommunications line cord." The rationale
for this line cord exemption is that a cord
of this size or larger will not melt through
and present a shock or fire hazard under the
equivalent energy contained in test condition
1 (600 V, 40 A, 1.5 seconds).
Pass section 6.3.3. Section 6.3.3
of the standard ensures that there is appropriate
electrical isolation of the telecommunications
network from ground. Compliance is checked
by inspection and by performing an ac or dc
insulation strength test at 1.5 kV between
the telecommunications network voltage (TNV)
circuit and unearthed parts of the equipment
expected to be held during normal use (e.g.,
telephone handset). For parts that can be
touched by a test finger or that provide connection
to other equipment, a voltage of 1.0 kV is
used. The test is conducted by slowly raising
the voltage to the appropriate level and holding
it for 60 seconds. Passing the test requires
that there be no insulation breakdown and
that current flow not exceed 10 mA. If surge
suppressors bridge the TNV circuit insulation,
they must have a minimum dc sparkover voltage
equal to 1.6 times the rated voltage of the
equipment (e.g., 120 or 240 V x 1.6). Surge
suppressors are typically removed during the
insulation strength test.
The rationale for this test comes from
the possibility that the telephone line may
be subject to power cross from the 120 V mains
circuit. Voltages of 1.0 or 1.5 kV ensure
the adequacy of the insulation under these
conditions. If the equipment is grounded,
surge suppressors will typically bridge the
TNV circuit and ground, and therefore must
be able to withstand the mains voltage with
some margin. An alternative procedure that
is allowed per the standard's Figure 18b (see
Figure 1) is to perform test 5 shown in Table
I (120 V, 25 A, 30 minutes).
Provide fire enclosure and spacings.
The most critical and often most difficult
element to meet in following the construction
path is to provide a fire enclosure with the
appropriate spacings. The spacings separate
the TNV circuit from internal materials, some
of which may be potentially flammable.
In the standard, a fire enclosure is
defined as a structure designed to minimize
the possible emission of flame, molten metal,
flaming or glowing particles, or flaming drops.
The enclosure must meet strict requirements
for the size and spacing of any holes in the
structure, depending on the materials used
for the enclosure and the flammability rating
of components enclosed within. The fire enclosure
itself must meet certain flammability tests
described in Annex A of the standard. These
tests involve applying the flame from a Bunsen
burner directly to the material (five applications
of five seconds duration each) and ensuring
that no flaming or molten materials fall from
the test sample and ignite a cheesecloth indicator.
To meet these requirements, fire enclosures
are typically made of either metal or specially
formulated flame-rated plastics.
The spacings requirement places an
additional burden on the construction. All
parts of the TNV circuit must be separated
from materials of flammability class V-2 or
lower by 25 mm of air or a flammability barrier
made from materials of class V-1 or better.
In addition, parts in the TNV circuit must
be separated from openings in the sides or
top of the fire enclosure by at least 25 mm
of air or a barrier of class V-1 or better.
The flammability class rating refers to the
resistance of these materials to combustion
after application of a direct flame, class
V-0 being the highest-rated material.
The use of fire enclosures has been
well established in the computer industry
as a way of mitigating potential hazards.
The addition of the spacings requirement is
a recognition that TNV circuits may be subject
to overvoltages as high as 600 V with energies
as much as 100 A2-seconds. Without
any overcurrent protection in place, these
fault conditions could produce arcing and
internal component explosions. By requiring
a fire enclosure and spacings, the standard
minimizes the possibility of an unsafe condition.
Construction Path with Current Limiting
This path, shown by the three diamonds
on the left-hand side of Figure 1, combines
current limiting and the use of a fire enclosure
to ensure the safety of information technology
equipment. A unique feature of this path is
that compliance with section 6 may be achieved
through inspection without performing any
testing, thus saving a manufacturer time and
money, and avoiding the risk of not passing
the tests. The three diamonds require limiting
fault energy, limiting current, and providing
a fire enclosure.
Limit fault energy to <100 A2-seconds.
This diamond establishes the requirement to
limit fault energy to less than 100 A2-seconds
per the 600-V, 40-A test condition 1 as described
in Table I. The standard allows that circuits
or components that have been listed to UL
497A or CSA C22.2 No. 226, "Secondary Protectors
for Communications Circuits," may be used
to meet this requirement without additional
testing. The overvoltage test requirements
of UL 497A and CSA C22.2 No. 226 are essentially
the same as those in UL 1459.
However, an information technology
equipment OEM must understand that UL 497A
is not a component specification, but is in
fact an equipment specification used for listing
multicomponent protection modules. As described
previously, if such a module is used in the
equipment, this diamond can be passed without
testing. UL is currently evaluating whether
certain discrete circuit protection components
could receive a recognition to UL 497A if
they pass key elements of the specification.
If UL grants this recognition, these discrete
circuit protection components could also be
used without testing the equipment.
Limit current to 1.3 A. Meeting the
requirements of this diamond requires that
the TNV circuit contains a method for limiting
current to 1.3 A maximum steady state that
is also compliant with UL 497A. An example
cited by the standard is a 1.0-A rated fuse.
Note that meeting the 1.3-A limiting specification
is not automatically achieved by meeting the
UL 497A requirements, an example being a 1.6-A
fuse that by definition will not limit current
to 1.3 A.
Provide a fire enclosure. The fire
enclosure requirements are described previously
in the construction path discussion. This
decision diamond does not require the additional
spacing conditions because current limiting
is already provided for in the previous diamonds.
As stated previously, a key benefit
of following this path is that performance
testing is not required. There is an alternative
to providing the fire enclosure, however,
which can be seen by following the "No" path
at the "Fire enclosure" decision diamond and
moving to the "Pass 2, 3, 4" diamond. Because
tests 2, 3, and 4 are also subsets of the
UL 497A requirements, circuit protection modules
or discrete components used to meet the "100
A2-seconds limiting" diamond should
also pass these tests.
Construction and Test Path
In working through the standard with
equipment manufacturers and UL, we found another
valid path we call the construction and test
path. This path involves meeting the requirements
of diamonds "Min. 26 AWG line cord," "Pass
6.3.3" or "Pass 5," and "Pass 2, 3, 4." This
path addresses the safety of the equipment
by testing to a subset of the overvoltage
tests (tests 2, 3, 4, and 5, or section 6.3.3),
and by ensuring the 100 A2-second
energy-withstand capabilities of the equipment
through use of the minimum 26 AWG line cord.
From an equipment design perspective,
this pathway is appealing because it bypasses
the potential engineering difficulties of
providing a fire enclosure with spacings.
In addition, it may be possible to design
circuit protection components that meet tests
2, 3, 4, and 5 and that are smaller and less
costly than devices that also must meet test
1. Such components would still provide some
level of current limiting, though clearly
less than those that meet the complete performance
path.
Choosing the Appropriate Path
Each of the potential paths provides
a means for designing safe equipment per the
overvoltage requirements of the standard,
but the paths are clearly not equivalent in
the equipment performance that results. By
using a fire enclosure and spacings to meet
the construction path, the equipment designer
is essentially controlling and limiting the
damage following an overvoltage event on the
telecommunications line. By using circuit
protection components, either for the performance
path or the construction with current limiting
path, the equipment designer meets the safety
requirement by limiting and interrupting current.
In addition, this type of protection provides
additional protection coordination with the
building wiring and primary overvoltage protection
devices. The latter benefit is not required
by the UL 1950 standard but may be desirable
in some installations.
Most traditional telephone equipment
manufacturers are likely to continue to use
discrete circuit protection components following
the performance path because the cost to upgrade
casings and providing for spacings to meet
the construction path will be prohibitive.
Computer OEMs, on the other hand, will often
follow the construction path because the computer
cases have already been designed to meet the
fire enclosure requirements. As long as the
cases are large enough and the TNV circuits
are designed to also meet the spacings requirements,
no overcurrent protection components will
be required. Some manufacturers of high-end
telephony equipment (e.g., PBX and key telephone
systems) are following the construction path
with current limiting, often using resettable
modules, because of the added reliability
in case of an overvoltage fault and because
they can achieve a listing by inspection without
undergoing the testing.
Manufacturers of small PC/telephony
devices and components are likely to choose
a path that avoids the "Fire enclosure and
spacings" diamond. For example, the draft
MiniPCI standard for small form factor modem
and network interface cards includes requirements
to meet UL 1950. However, the form factor
is so small that it will not be possible to
meet the spacings requirement of the construction
path. Thus, there seems to be a market opportunity
for smaller and less expensive overcurrent
protection components to help these card manufacturers
meet the construction and test path.
Protection Solutions to UL 1950 and FCC
Part 68
When information technology equipment
OEMs evaluate possible circuit protection
solutions to UL 1950, either performance path
or construction and test path, they must also
consider the coordination of performance with
the overvoltage protection devices used to
meet FCC Part 68 lightning requirements. FCC
Part 68 approval is required for all equipment
that is to be connected to the U.S. telecommunications
network. The FCC test requirements are shown
in Table II.
|
Surge
|
Waveform
(open circuit)
|
Peak
Voltage
(open circuit)
|
Waveform
(short
circuit)
|
Peak
Current
(short circuit)
|
Number of
Hits
|
Test
Result
|
|
Type
A metallic
|
10/560
|
800
|
10/560
|
100
|
2
|
A
|
|
Type
A longitudinal
|
10/160
|
1500
|
10/160
|
200
|
2
|
A
|
|
Type
B metallic
|
9/720
|
1000
|
5/320
|
25
|
2
|
B
|
|
Type
B longitudinal
|
9/720
|
1500
|
5/320
|
37.5
|
2
|
B
|
Table II. FCC Part 68
lightning test requirements. Under test
result A, the product must remain safe,
with the integrity of network maintained
(R > 5 M ),
and under test result B, the product must
not cause permanent opening or shorting.
|
Typical protection circuits for ungrounded
and grounded equipment are shown in Figures
2 and 3. Examples of overcurrent protective
devices include "telecom"-rated fuses and
PTC devices made from either polymeric or
ceramic materials. Examples of overvoltage
protection devices include metal oxide varistors,
thyristors, and diodes.
 |
| Figure 2. Protection scheme for ungrounded
equipment. |
 |
| Figure 3. Protection scheme for grounded
equipment. |
In 1998, the FCC added the Type B surges
described in Table II to improve the robustness
to lightning of telecommunications equipment.
FCC requirements state that this lightning
surge must not cause any opening or shorting
of the equipment. For example, if a fuse is
used for overcurrent protection, then it must
not blow during the test surge.
Use of PTC devices for overcurrent
protection provides an additional benefit
because they are self-resetting. Thus, even
if the information technology equipment experiences
a fault, the PTC device will protect the equipment
and allow it to continue operation after the
fault is removed. Figure 4 shows one potential
solution for resettable protection of ungrounded
customer premises equipment to meet the UL
1950 performance path and FCC Part 68. Though
not required by the FCC, many OEMs design
their equipment to also pass the Type A surge
without opening or shorting. This practice
leads to better lightning-withstand performance
but can create other problems in coordinating
protection with downstream components, including
the overvoltage device.
Typical overvoltage protection devices,
such as thyristor surge suppressors, will
have a "breakover" voltage (i.e., the voltage
at which the device changes from highly resistive
to highly conductive) of 250 to 400 V. Thus,
the 600 V applied during tests 1, 2, and 3
will cause the thyristor to conduct, and current
will flow through the thyristor between tip
and ring. The coordination graph comparing
time-to-trip of a resettable fuse and time-to-damage
for a 270-V, 50-A-rated thyristor (see Figure
5) shows that under all fault current conditions,
the resettable fuse trips before the thyristor
is damaged. Also, the resettable fuse does
not trip during FCC Type A or Type B surges,
meaning protection coordination and a fully
resettable protection solution are achieved.
 |
| Figure 4. Resettable protection solution
for UL 1950 performance path and FCC Part
68. |
 |
| Figure 5. Comparison of time-to-trip
and time-to-damage curves for thyristors
and resettable fuses. |
Further consideration of the interaction
between overcurrent and overvoltage protection
devices can lead to cost savings. The thyristor
in the above example has a rating of 70 A
in the FCC Type A 10/560 microsecond test30
A less than the required 100-A performance.
However, as long as the resettable fuse has
a minimum resistance of 3.5 ,
the actual current through the thyristor will
be
Thus, the smaller, less expensive thyristor
may be used with the minimum 3.5-
resettable fuse while still meeting the FCC
requirements.
The new UL 1950 3rd ed. standard for
information technology equipment is a major
step forward in standards integration. For
equipment connected to telecommunications
networks, OEMs have several options for meeting
the requirements, including construction options
using fire enclosures and spacings and performance
paths incorporating circuit protection components
or modules. A complete protection solution,
one that meets the requirements of the standards
and produces a more-reliable information technology
product, can be achieved through careful coordination
of the protection components.
Gary H. Wiseman (gwiseman@raychem.com)
is marketing director for Raychem Circuit Protection
Products, a division of Tyco Electronics Group
(Menlo Park, CA). His degrees include a PhD
in chemistry from MIT. Also working for the
Circuit Protection Products group at Raychem
is Mario H. Gomez (mgomez@raychem.com),
product compliance manager. Gomez has participated
in many areas of product safety, including the
development of today's product safety standard
IEC 60950.
Back to September/October
Table of Contents
|
|