Improving Safety and Performance with Dc Dielectric
Testing
Jeffrey
Gray
Dc
and ac testing provide an equivalent level of breakdown
detection, but the increased accuracy of dc leakage-current
detection can reveal marginal insulation systems.
Dielectric
withstand testing is used to evaluate wiring insulation.
When testing insulation installed in mobile homes, it
is important that the insulation be tested at a much greater
voltage than normal to ensure that the insulation is not
marginal. If voltages are set correctly, dielectric withstand
testing using a dc voltage provides the same outcome as
using an ac dielectric test. In addition, dc testing offers
significant safety and performance improvements over ac
testing.
Dielectric
testing is a simple, nondestructive method of verifying
the adequacy of electrical insulation to withstand transient
(surge) events. Transient voltage spikes on power lines
are generally the result of nearby lightning strikes,
but spikes can also occur for other reasons. In general,
such transient spikes have a very short duration--the
spike lasts for <20 microseconds.
A
dielectric test can verify the performance headroom of
the insulation, ensuring that the insulation will not
fail because of insulation degradation from aging, moisture,
wear due to vibration, or other causes.
The
voltage level of the dielectric test is generally adjusted
based on the environmental conditions to which the end
product will be subjected. A higher dielectric test voltage
is used for equipment located where environmental conditions
are more severe. Passing this more-severe dielectric strength
test when the end product is new indicates that the insulation
being stressed has enough headroom to provide adequate
protection after the end product has been subjected to
environmental degradation.
Test
Method. In dielectric testing, a high voltage (typically
≥1000 V) is applied between two conductors that
are supposed to be electrically insulated from each other.
If the two conductors (e.g., an insulated live wire and
a metal enclosure) are completely isolated from one another,
then the application of a large voltage difference between
the two conductors would not allow current to flow between
the conductors. In this case, the insulation is said to
withstand the application of a large voltage potential
between the two conductors, hence the term dielectric
withstand test.
In
general, two dielectric test results indicate insulation
failure. The first is excessive current flow during the
test due to low insulation resistance of the insulating
material separating the two conductors. The second is
an abrupt dielectric breakdown due to electrical arcing
or discharge, either through the insulation material,
over the surface of the insulation material, or through
the air.
Test
Voltage. If the test voltage is too low, the insulation
material will not be adequately stressed during the test,
allowing inadequate insulation to pass the test. On the
other hand, if the test voltage is too high, the test
could cause permanent damage to an insulation material
that is otherwise adequate for the application. A general
rule of thumb used for testing mains wiring that operates
at voltages of 120240 V ac is 1000 V plus two times
the operating voltage. Using this rule, 120-V wiring would
be tested using a voltage of 1000 V + (2 x
120 V) = 1240 V ac.
Test
Duration. To adequately stress the insulation, the
test voltage is generally applied for 1 minute. However,
many standards allow the test duration to be reduced to
1 second for production line testing to accommodate the
large volume. For reduced-duration testing, standards
often require the test voltage to be increased by 20%
to ensure that 1 second is sufficient to test the insulation
adequately.
Ac
versus Dc
Test
Waveform. The nominal line voltage in the United States
is 120 V ac. The waveform of the voltage is sinusoidal,
and the frequency of that voltage is 60 Hz (cycles per
second). The voltage of 120 V refers to the root-mean-square
(rms) value of the ac voltage. The rms value of an ac
voltage provides a mathematical equivalent to the heating
value of a dc voltage. In other words, an ac voltage of
120 V rms applied to a resistor (or a nichrome wire heater)
would generate the same heat output as when a dc voltage
of 120 V (e.g., from a battery) is used.
The
instantaneous voltage of 120 V ac at 60 Hz varies with
time. In one cycle, which repeats 60 times per second,
the voltage will start at 0 V, increase to a peak of about
170 V, drop down to 0 V again, continue to drop to a negative
peak of 170 V, and then increase again to 0 V (see
Figure 1). Taking the simple average of the voltage over
one cycle results in a value of 0 V. Calculating the rms
value results in a measurement of 120 V. By definition,
the peak of a sinusoidal waveform is the rms value times
the square root of 2 (i.e., Vpeak
= Vrms x
1.414). Figure 2 shows an ac waveform with an rms voltage
of approximately 1000 V. Note that the positive and negative
peaks of the waveform exceed +1400 V and 1400 V,
respectively.
 |
|
Figure
1. A 120-V ac rms waveform at 60 Hz.
|
| |
 |
|
Figure
2. An ac waveform with an rms voltage of about 1000
V.
|
Test
Voltages. The intent of the dielectric test is to
stress the insulation for a short period of time and check
that it does not fail. Testing using a 60-Hz ac voltage
is done only as a matter of convenience--a transformer
with a high-voltage secondary winding (e.g., a neon-sign
transformer) can be used to generate the high voltage
needed to perform the dielectric test. A 60-Hz ac test
voltage cannot simulate real-world events any better than
a dc test voltage can. Even high-voltage transients (surges)
that appear on the 120-V ac mains are not ac; they are
momentary voltage spikes with a typical duration that
is measured in microseconds (millionths of a second) or
milli-seconds (thousandths of a second).
Any
decisions regarding the use of ac versus dc voltage for
testing must consider the intent of the test, which is
to stress the insulation being tested. The higher the
voltage, the more stress is applied to the insulation.
When an ac test voltage is used, the highest amount of
stress is applied to the insulation at the moments when
the test voltage is at a positive or negative peak. At
other points of the sinusoidal ac waveform, the electrical
stress is lower.
An
ac test voltage of 1000 V rms will have voltage peaks
of 1414 V. Therefore, if a dc test voltage is used, the
test voltage must be increased to 1414 V dc to produce
the same level of stress to the insulation as would 1000
V ac rms. The dc test voltage is shown in Figure 3. Note
that the peak test voltages in both Figures 2 and 3 are
the same.
 |
|
Figure
3. A 1414-V dc test voltage.
|
The
difference in test voltage for dc compared with ac is
supported by national testing and standards writing organizations
such as Underwriters Laboratories, Factory Mutual Corp.,
the Institute of Electrical and Electronic Engineers,
and the American National Standards Institute, as well
as international organizations such as the International
Electrotechnical Commission.
Dielectric
Breakdown Evaluation. Because the electrical stress
on the insulation is highest at the peak of the ac waveform,
dielectric breakdown occurs at the peak of an ac test
voltage. Figure 4 is an oscilloscope display of an ac-voltage
dielectric breakdown. Note that the waveform is smooth
as the voltage increases to the peaks, then abruptly breaks
down at the peak voltage. Figure 5 shows the occurrence
of a similar dc-voltage breakdown.
 |
|
Figure
4. An ac-voltage dielectric breakdown.
|
| |
 |
|
Figure
5. A dc-voltage dielectric breakdown.
|
It
is important to note how abruptly a dielectric breakdown
occurs. In Figure 6, the ac breakdown in Figure 4 has
been expanded 50,000 times--the time base on the oscilloscope
has been changed from 5 milliseconds to 100 nanoseconds
to zoom in on the breakdown event. The time that it takes
for the voltage to drop from the peak value to 0 V is
10 nanoseconds, approximately a million times faster than
the period of the 60-Hz ac test voltage waveform.
 |
|
Figure
6. A zoomed-in ac breakdown.
|
Because
the breakdown occurs so quickly, and because it occurs
at the peak voltage of the ac waveform, the ac and dc
voltages appear exactly the same to the breakdown; that
is, it appears as a peak voltage of very long duration.
In other words, the peak voltage of the ac waveform lasts
much longer than the breakdown itself.
Figure
7 illustrates a breakdown similar to that shown in Figure
6, except the test was conducted using a dc voltage of
1.414 times the rms value of the ac waveform. A comparison
of Figures 6 and 7 shows that the behavior of a breakdown
under both ac and dc conditions, respectively, is identical.
 |
|
Figure
7. A zoomed-in dc breakdown.
|
Advantages
and Disadvantages. Historically, dc test voltages
are more difficult to generate, resulting in the need
for more-costly, complicated test equipment. This disadvantage
is offset by the performance and safety advantages gained
from using dc test voltages. To explain these advantages,
some additional background information is needed.
An
electric charge develops whenever a voltage difference
is applied between two conductors that are separated by
an insulator. The amount of charge created is proportional
to the voltage applied and to the capacitance between
the two conductors. If charge is represented by Q,
voltage by V, and capacitance by C, then
the mathematical relationship between these three quantities
can be represented as Q = C x
V.
In
practical applications, capacitance can exist due to discrete
capacitors, but capacitance can also be created inadvertently
when two conductors with a voltage difference are placed
close together. Examples of this type of capacitance can
be found in electric motors, transformers, multiconductor
electrical wiring, and single-conductor wiring that is
routed near metal. If the voltage is varied, the charge
varies. If the voltage swings in both positive and negative
directions, then the charge will do the same.
A
second fundamental concept is that electric current will
flow through a capacitor whenever the voltage changes.
This is because as the voltage is increased across a capacitor,
the amount of charge increases. Electric current is simply
a measurement of how much the charge changes over a period
of time. Current is often represented by I, which
is measured in amperes, or amps. The amount of charge
Q is measured in coulombs. One amp of current is
defined as a charge flow of 1 coulomb per second.
Combining
the concept of capacitance with that of current yields
the following. A changing voltage generates a changing
charge. By definition, this changing charge is the flow
of electric current. Therefore, a changing voltage causes
current to flow between two conductors. Because of the
capacitance between the two conductors, this current can
flow between them even when they are physically insulated
from each other. The greater the capacitance is between
the conductors, the greater the current flow will be.
When
performing dielectric tests using an ac test voltage,
an electric current will flow between the two points being
tested (due to the capacitance between the two conductors).
This current does not represent a failing test result
from having a low insulation resistance. Therefore, an
ac dielectric tester must compensate for this allowable
flow of current. The most common method to accomplish
this is to allow the tester to detect a significant amount
of current (typically ≥20 mA) without indicating an
excess current failure. If multiple products are tested
with the same dielectric tester, this current-limit set
point may need to be adjusted even higher to accommodate
the equipment with the greatest capacitance between the
conductors being tested. In other words, the dielectric
tester must be desensitized so that it will ignore current
levels <20 mA (for example). This situation creates
two very dangerous problems.
The
desensitized ac dielectric tester cannot tell the difference
between 5 and 15 mA. Consider what happens if the circuit
under test has capacitance between the conductors that
causes 5 mA to flow in normal conditions during the test.
A device under test (DUT) with faulty insulation that
allows 300% of the normal amount of current to flow (15
mA) would still be considered an acceptable test result
by the desensitized ac dielectric tester.
The
desensitized ac dielectric tester can supply a lethal
amount of current to the human body and still not shut
down due to excess current. For example, if the DUT is
sinking 5 mA, and the test operator comes in contact with
the test voltage such that 10 mA flows through the operator,
a total of 15 mA would be sourced by the tester. Because
15 mA is less than the 20 mA current-limit set point,
the tester does not shut down, allowing the operator to
be seriously injured or killed.
When
performing dielectric tests with a dc test voltage, electric
current flows only while the voltage is being ramped up
from 0 V to the final test voltage. In this case, the
current flow is very small because the voltage is typically
ramped up over a period of 12 seconds, compared
with an ac test voltage that goes from a positive peak
to a negative peak and back again 60 times per second
(remember that the current flow is proportional to the
change in voltage over time). In fact, a dc test voltage
that is ramped up over a period of 2 seconds causes only
1/120
(<1%) of an ac test voltage's current flow. As soon
as the dc voltage reaches the final test level, the current
essentially stops altogether. In most cases, the amount
of current that flows during a dc dielectric test is negligible,
regardless of the amount of capacitance that exists in
the DUT.
When
compared with an ac dielectric test, dc testing offers
many advantages. The maximum allowable test current can
be set to a much lower level (1 mA is typical). The dc
tester shuts down when more than 1 mA of current flows
during the test. This highly sensitive test allows the
operator to identify marginal constructions that would
have been overlooked by an ac tester.
The
lower test-current levels are significantly safer for
the operator. At 1 mA, the current is enough to shock
the operator, but the test current would be automatically
shut off when the current flow exceeds 1 mA.
Conclusion
The
question of whether to use ac or dc dielectric testing
has nothing to do with the fact that the insulation being
tested is normally subjected to 120 V ac. A dielectric
breakdown occurs in nanoseconds. All of these events happen
so quickly that a varying 60-Hz ac voltage effectively
becomes an unchanging dc voltage. If the peak voltages
of an ac and dc dielectric withstand test are the same,
then both types of testing can verify the suitability
of insulation used between conductors. For the peak voltages
to be equal, the dc voltage used in a dielectric withstand
test must be 1.414 times the ac rms voltage used.
Dc
testing offers significant advantages over ac testing.
Dc and ac testing provide an equivalent level of breakdown
detection due to total insulation failure. However, the
heightened accuracy of dc leakage-current detection allows
marginal insulation systems to be detected. Dc dielectric
testing is superior for ensuring operator safety. Neglecting
to consider dc testing as an alternative to ac testing
potentially jeopardizes both the test operator (with shock
hazards during testing) and the consumer (with marginal
insulation).
Jeffrey
Gray is the president of Compliance West USA (San Diego,
CA).
Back
to 2002 Annual Reference Guide Table of Contents
|