Power Protection in Equipment: A Source of Confusion
Clarified
Andrew
DeIonno
Supplementary
protectors are recognized power-protection components
that are circuit breakers but also, importantly, something
less.
 |
|
Illustration
by TAISHA PAYTON
|
Many
laboratory field engineers and electrical inspectors can
testify that the following scenario is not uncommon: A
facility needs some noncertified equipment to be inspected
before the plant can become operational. Perhaps it is
only a simple machine with a few motors and a small industrial
control panel, a system that runs at 15 A and is on a
30-A branch. Upon examining the machine, the inspector
or engineer comes across a device that, although it is
a recognized circuit-breaking component, seems unlikely
to be one that is acceptable for the application under
inspection.
Equipment
manufacturers usually regard any certified device that
looks and seems to act like a circuit breaker as a circuit
breaker per se. However, some devices that look like circuit
breakers have limited application; their use in situations
calling for a listed circuit breaker can raise safety
issues. Known as supplementary protectors, they
are recognized components. Supplementary protectors are
not, as their name suggests, designed to provide primary
power protection in equipment that supplies mains power
to other equipment.
This
article clarifies the often-confusing terminology and
identifies applications for which circuit breakers and
supplementary protectors are appropriate.
Devices
for Overcurrent Protection
What
exactly is a circuit breaker? The 1999 version of the
National Electrical Code (NEC) defines a circuit breaker
as "a device designed to open and close a circuit by nonautomatic
means and to open the circuit automatically on a predetermined
overcurrent without damage to itself when properly applied
within its ratings." Overcurrent in turn is characterized
as "any current in excess of the rated current of equipment
or the ampacity of a conductor. It may result from overload,
short circuit, or ground fault."1
The
molded-case circuit breaker standard (UL 489) lists specific
devices that are "intended to provide service entrance,
feeder, and branch circuit protection in accordance with
the National Electrical Code, NFPA 70."2 Some
applications of molded-case circuit breakers are outlined
in Article 210-52 (Conductor Protection) and Article 430-52
(Motor Protection) of the 1999 code.
And
what, then, is a supplementary protector? Article 240-10
of the 1999 version of the NEC establishes clearly the
differences between circuit breakers and supplementary
protectors: "Where supplementary overcurrent protection
is used for lighting fixtures, appliances, and other equipment
or for internal circuits and components of equipment,
it shall not be used as a substitute for branch-circuit
overcurrent devices or in place of the branch-circuit
protection specified in Article 210. Supplementary overcurrent
devices shall not be required to be readily accessible."
The
supplementary protector standard (UL 1077) recognizes
devices that are "intended for use as overcurrent, or
over- or under-voltage protection within an appliance
or other electrical equipment where branch circuit overcurrent
protection is already provided, or is not required."3
It is important to note that supplementary protectors
do not meet the strict NEC requirement for branch-circuit
overcurrent protection quoted above. These devices are
intended only to protect equipment components in specific
applications.
The
significant differences between listed molded-case circuit
breakers and supplementary protectors are outlined in
Table
I. Despite the notable divergence in these devices'
capabilities and purposes, supplementary protectors and
circuit breakers are often confused. The confusion can
be attributed to a variety of factors.
First,
supplementary protectors are often referred to as circuit
breakers for equipment (abbreviated as CBE) or miniature
circuit breakers (MCBs). In related literature and
advertising, these devices may be called circuit breakers,
leading designers to incorrectly conclude that they will
perform like molded-case circuit breakers. Supplementary
protectors also look very similar to molded-case circuit
breakers, and thus are thought by designers to provide
equivalent protection.
Another
problem is that manufacturers of supplementary protectors
do not always clearly indicate that suitable branch protection
or in-line fusing is required in certain applications.
Such an indication explicitly shows the inappropriateness
of relying on the protectors to fulfill circuit-breaker
functions.
Finally,
European manufacturers use supplementary protection for
circuit-breaking in equipment. European equipment imported
into the United States is generally used in industrial
settings in which equipment wiring is provided remotely
from the control panel. Such wiring is a violation of
the NEC if it is protected by a supplementary protector.
Evaluating
the Usability of Supplementary Protectors
The
usability of a supplementary protector beyond its incorporation
into a listed appliance or assembly is very limited. How
can a design engineer determine whether a supplementary
protector will be acceptable in an application? The National
Electrical Code, NFPA 79 (the electrical standard for
industrial machinery), and UL 508A (governing industrial
control panels) are examples of product standards that
provide guidance in determining the acceptability of a
supplementary protector for a particular use. The flowchart
in Figure
1 can help to evaluate its suitability. However, use
of the flowchart should not be substituted for careful
review of the applicable end-product standard.
Figure
2 diagrams a simple circuit that invites consideration
of the possible applicationand misapplicationof a
supplementary protector. For example, a designer can apply
the decision chart in Figure 1 and assume that the fuse
in Figure 2 has not been installed originally as part
of the circuit. The circuit diagram then provides guidance
on the proper installation of the supplementary protector.
 |
|
Figure
2. Schematic circuit diagram of a control panel
with a supplementary protector.
|
If
a short circuit or overload occurs on the load side of
the supplementary protector in the diagram, then the only
protection provided would be through the 100-A branch
circuit. The 14 AWG conductor is not protected by the
100-A circuit breaker as required by the NEC.
The
added fuse, sized appropriately for the voltage, supplies
the needed branch-circuit protection. In this case, it
would need to be sized at 15 A. With the addition of the
fuse, the supplementary protector would be sufficient
for the application in the figure. The fuse protects the
branch-circuit conductor on the line and load side of
the supplementary protector.
Conclusion
Supplementary
protectors are circuit-protection devices that, like any
other recognized component, must be used properly when
incorporated into equipment and appliances. Engineers
creating or reviewing a design that includes a device
that looks like a circuit breaker (both on paper and in
fact) must be sure to evaluate the circuit for proper
branch-circuit protection. Supplementary protectors have
very limited utility in applications involving appliances
or assemblies that are not listed. Designers or manufacturers
of an appliance or assembly should always request information
regarding the conditions of acceptability for any supplementary
protector being considered for use. This information helps
confirm that the recognized component will be employed
in accordance with its certification limitations.
References
1.
ANSI/NFPA 70, National Electrical Code, National
Fire Protection Agency, 1999.
2.
UL 489, Molded-Case Circuit Breakers, Molded-Case Switches,
and Circuit Breaker Enclosures, 9th ed., Underwriters
Laboratories, 1996.
3.
UL 1077, Supplementary Protectors for Use in Electrical
Equipment, 5th ed., Underwriters Laboratories, 1999.
Andrew
DeIonno is senior engineer for MET Laboratories (Morrisville,
NC). He can be reached at drewd@productsafet.com.