|
|
|
|
|
|
|
Electrical Safety of Dc Telephone Systems
Moe
Lamothe
Proper
classification is crucial to the electrical safety of
telephone systems.
Preventing
shock or fire is the primary goal behind many electrical
safety standards. The electrical safety of telephone interfaces
must be addressed because these interfaces produce voltage
levels severe enough to present either a shock or a fire
hazard.
Several
standards address this issue, so confusion over the proper
classification of dc-powered telephone equipment with
respect to the power interface is common. This article
discusses how to properly classify telephone interfaces
when considering the potential electrical shock hazard,
as outlined in several key standards and guidance reports:
International Electrotechnical Commission (IEC) 60950,
3rd ed., IEC Technical Report (TR) 62102, and European
Telecommunications Standards Institute (ETSI) 300 001
and 300-132-2.14
Power
Requirements
For
clarity, voltage levels are referenced in this article
as positive voltages rather than as a mix of positive
and negative voltages. Telephone equipment used in central
offices is typically dc-powered at either 48 or 60 V dc
(72 V dc with battery float voltages). The dc source must
be classified properly when examining the equipment for
safety.
North
America has long used a standard of 48 V dc for the feed.
Even considering the battery float voltage, the measured
voltage still falls below the 60-V-dc hazardous voltage
limit. For this reason, 48-V-dc systems are often considered
separated extra low voltage (SELV). As defined in standards
such as IEC 60950, such systems are classified as a telephone
network voltage, TNV-2 or TNV-3.
Europe
is also moving toward a standard of 48 V dc, but many
telephone installations still use a 60-V-dc supply voltage.
The float voltage level of 72 V dc increases the voltage
to what could be considered a hazardous level.
Because
the dc voltage is typically derived from an ac source,
basic insulation from the ac source usually makes the
dc supply a secondary circuit. In this situation, the
dc power feed would be properly classified as TNV-2 or
TNV-3, depending on the network environment. The network
environment is defined as the external conditions
to which the telephone system is exposed.
Circuits
IEC
60950, 3rd ed., provides clear definitions of TNV circuits.
Both TNV-2 and TNV-3 are particularly relevant to dc-powered
telephone systems. According to IEC 60950, a TNV circuit
is a circuit in the equipment to which the accessible
contact area is limited. It is designed and protected
so thatunder normal operating and single-fault conditionsthe
voltages do not exceed specified limit values. A TNV circuit
is considered to be a secondary circuit as defined in
IEC 60950. TNV circuits are classified as TNV-1, TNV-2,
or TNV-3.
TNV-2
Circuit. This is a TNV circuit whose normal operating
voltages exceed the limits for a SELV circuit under normal
operating conditions. These circuits are not subject to
overvoltages from telecommunication networks.
TNV-3
Circuit. This is a TNV circuit whose normal operating
voltages exceed the limits for a SELV circuit under normal
operating conditions. Overvoltages from telecommunication
networks are possible for TNV-3 circuits.
Standards
Development
Historically,
the electrical safety of telephone systems was determined
by the Bell System (AT&T), and later by the regional
Bell companies. With industry deregulation in North America,
CSA International (CSA) and Underwriters Laboratories
Inc. (UL) began developing electrical safety standards
to ensure operator and user safety. These standards were
crucial because the Bell operating companies no longer
had close control of the installed products.
In
the early 1980s, the first electrical safety standard
developed by CSA was CSA C22.2 No. 0.7, "Equipment Electrically
Connected to a Telecommunication Network."5
This standard was later replaced by CSA C22.2 No. 225,
"Telecommunication Equipment."6 This was a
stand-alone standard rather than a reference standard
for other safety standards. Section 6 of CSA C22.2 No.
60950 (and the preceding CSA 22.2 No. 950) also included
telephone-interface requirements different from those
contained in C22.2 No. 225. No. 225 has now been dropped
in favor of the binational (Canada and United States)
C22.2 No. 60950.7
In
the late 1980s, UL developed UL 1459, which contained
many new requirements loosely based on both the Bell and
CSA C22.2 No 225 requirements.8 Many additional
requirements introduced into UL 1459 were eliminated when
UL 60950 (and the preceding UL 1950) became the standard
of choice. This binational standard includes hazard tests
for telephone interfaces that are not included in the
equivalent international IEC 60950 standard.
In
1991, Europe published EN 41003, "Particular Safety Requirements
for Equipment to be Connected to Telecommunication Networks."9
This standard was used for telephone interface safety
in Europe. The requirements in this standard were later
folded into as the now-familiar section 6 of IEC 60950.
Although IEC 60950 does not yet contain hazard tests for
evaluating interfaces for telephone equipment, there is
an indication that such tests will be included in future
versions.
IEC
Technical Report 62102
Several
classifications of interface equipment can be connected
to information and communications equipment. "Classification
of Interfaces for Equipment to be Connected to Information
and Communications Technology Networks," IEC TR 62102
was issued in March 2001. This technical report addresses
various telephone-interface signals and battery-feed options.
It classifies circuits as either Network Environment 0
or Network Environment 1. If the network environment can
be classified as 0, then the equipment installed can be
evaluated to TNV-2 requirements; Network Environment 1
requires equipment evaluated to TNV-3.
The
following list summarizes the requirements for Network
Environment 0:
-
The
effect of indirect lightning (i.e., lightning that does
not directly strike the network conductors but nevertheless
induces a voltage in them) has been reduced.
-
Different
earth potentials at different points on the network
have been reduced to a level so that electric shock
is unlikely.
-
Power
cross or contact between the network and the ac mains
supply is unlikely.
-
Mains-induced
transients, surges, and power faults (due to capacitive,
inductive, or common-impedance coupling) are unlikely
to be caused by electrical isolation from or physical
coordination of the network conductors and the wiring
of the ac mains supply.
-
Voltages
induced by electrical traction are unlikely. Sufficient
distance must be provided between the telecommunication
network and such traction systems.
European
Requirements
For
Europe, telephone-interface requirements are specified
in ETSI standards. Although there are still many country-specific
deviations, ETSI standards are intended to minimize the
differences and reduce duplicated testing.
ETSI
300 001: "Attachments to Public Switched Telephone
Network (PSTN); General Technical Requirements for Equipment
Connected to an Analogue Subscriber Interface in the PSTN."
This standard specifies the requirements for equipment
that is connected to the PSTN. For this standard, the
dc supply may be a 48- or 60-V battery. Such equipment,
which often has ring voltage present, is typically supplied
with dc operating power via the telephone line. In this
case, the supply source does not meet the Network Environment
0 requirements. Because it falls under Network Environment
1, it must be evaluated as a TNV-3 supply, regardless
of the input voltage rating. Even if the equipment uses
60-V dc power (making an operating voltage of 72 V dc),
it must still be evaluated as a TNV-3 circuit. It can't
be considered a TNV-2 circuit even if the supply voltage
is less than 60 V dc.
ETSI
300 132-2: "Equipment Engineering (EE); Power Supply
Interface at the Input to Telecommunications Equipment;
Operated by Direct Current (dc)." This standard specifies
the requirements for systems where the battery power is
supplied by an in-plant dc power source (such as a battery
bank), or an ac power supply with a dc output. The dc
supply may be a 48- or a 60-V battery. In this case, the
supply source does meet Network Environment 0 requirements
because it is not normally exposed to an outside-plant
source. As a Network Environment 0, it can be evaluated
as a TNV-2 supply. Even if the equipment uses 60-V dc
power (making an operating voltage of 72 V dc), it is
still evaluated as a TNV-2 circuit because the dc supply
is a secondary circuit.
North
American Requirements
The
North American version of IEC 60950 (CSA C22.2 No. 60950/UL
60950) includes a clause that provides special considerations
for equipment connected to a centralized dc power system
(dc mains voltages). For such equipment, the dc mains
voltages are considered secondary circuits and are characterized
as either SELV circuits or hazardous-voltage circuits,
depending on the maximum operating voltage (including
the float voltage) of the source. When applying insulation
requirements, dc mains voltages are treated as a particular
type of circuit depending on the voltage level: SELV circuit
(up to 60 V), TNV-2 circuit (>60 V, up to and including
80 V), or hazardous voltage (>80 V). These circuits
are not subjected to TNV-circuit current limits when providing
power for centralized dc equipment. However, they must
meet appropriate current limits when connected to a telecommunications
network.
It
is important to note the use of the words characterized
and treated in these requirements. They indicate
clearly that although voltages may be considered hazardous,
they are not necessarily evaluated as hazardous voltages.
Centralized
Dc Power Systems
A
centralized dc power-distribution system consists of open
batteries, charger and rectifier circuits, and primary
and secondary distribution equipment to provide power
to equipment loads. Systems rated not less than 48 V have
one point directly earthed. Protective earth conductors
connect the exposed conductive parts of the installation
to that point. Systems rated less than 48 V may have one
point directly earthed.
Two
types of systems are recognized based on the arrangement
of earthed and protective earth (earthing) conductors:
-
Source-earthed
dc power systems in which the connection to the earthing
electrode is located at the source. Separate earthed
and protective earth conductors are provided throughout
the system.
-
Dc
power system earthed at the equipment location in which
the connection to the earthing electrode is located
in the area where the load equipment is to be installed.
This area is typically known as the earthing window.
General
Requirements. A centralized dc power system is considered
to be a secondary circuit. Equipment to be connected to
these systems must comply with the requirements in CSA
22.2 No. 60950/UL 60950. Requirements include:
-
Connections
to the system are subject to the requirements for primary
circuits and must meet the requirements for ac mains
supplies in section 3.2.
-
Provisions
for protective earthing must comply with the specification
in section 2.6.
-
If
the earthed supply conductor is connected to the equipment's
earthing conductor or to the frame of the equipment,
protective earthing must be in accordance with Clause
NAB.3 (see "Special Requirements" sidebar, p. 58).
-
Unless
otherwise specified by the manufacturer via means such
as a marking, a documented installation practice, or
a product specification sheet, the voltage ranges for
testing must be 40 V dc and 56.7 V dc for nominal 48-V-dc
systems, and ±20% for nominal 60-V-dc systems.
Voltages less than 10% or more than 6% of the
stated nominal voltage must not be used unless the unit
will be installed only on proprietary systems. For such
systems, manufacturers must be able to demonstrate that
the voltage regulation cannot exceed the manufacturer's
stated limits.
Conclusion
Dc
equipment is usually evaluated as having an input that
is classified as TNV-2 because the source can be reasonably
protected from overvoltages. Equipment such as a single-line
telephone is usually evaluated as having a TNV-3 input
because the dc source is often exposed to potential overvoltages.
Because
the input for dc-powered telephone equipment meets TNV-2
or TNV-3 requirements as defined in the safety standards,
it would be highly unlikely that such equipment would
be evaluated as having Class I input. To ensure the safety
of dc-powered equipment, proper classification is imperative.
References
1. IEC
60950, 3rd ed., "Safety of Information Technology Equipment,"
International Electrotechnical Commission (IEC), Brussels,
1999.
2. IEC
Technical Report 62102, "Classification of Interfaces
for Equipment to be Connected to Information and Communications
Technology Networks," IEC, Brussels, 2001.
3. ETSI
300 001, "Attachments to the Public Switched Telephone
Network (PSTN); General Technical Requirements for Equipment
Connected to an Analogue Subscriber Interface in the PSTN,"
European Telecommunications Standards Institute, Brussels,
1998.
4. ETSI
300-132-2, "Environment Engineering (EE); Power Supply
Interface at the Input to Telecommunications Equipment;
Part 2: Operated by Direct Current (dc)," ETSI, Brussels,
2001.
5. CSA
C22.2 No. 0.7, "Equipment Electrically Connected to a
Telecommunication Network," Canadian Standards Association
(CSA), Toronto.
6. CSA
C22.2 No. 225-M90, "Telecommunication Equipment," CSA,
Toronto.
7. C22.2
No. 60950, "Safety of Information Technology Equipment,"
CSA, Toronto.
8. UL
1459, "Standard for Safety of Telephone Equipment," Underwriters
Laboratories Inc., Northbrook, IL.
9. IEC/EN
41003, "Particular Safety Requirements for Equipment to
be Connected to Telecommunication Networks," IEC, Brussels.
10.
UL 891, "Standard for Safety for Dead-Front Switchboards,"
UL, Northbrook, IL, 2000.
11.
CSA C22.2 No. 31, "Switchgear Assemblies," CSA, Toronto.
Moe
Lamothe is the president of M.A. Lamothe & Associates
Inc. (Georgetown, ON, Canada). He can be reached at moe@lamothe-approvals.com.
|
|