|
The Role of Precompliance Testing in Electrical Product Safety
Basic electrical safety testing during early stages of production
can improve a manufacturer's bottom line and make an eventual product
recall less likely.
The
well-established practice of precompliance testing offers the advantage
of ensuring that an electrical product is designed and constructed so
as to meet necessary performance levels before the manufacturer has
become committed to full-scale production of the product as is. However,
in many organizations, safety testing of the product is one of the final
stages of the manufacturing process. The expectation is that the product
will pass a scheduled sequence of safety and performance tests, after
which it can be released for sale in the marketplace. (This article
pertains to electrical products manufactured for sale within the European
Union [EU]. All discussion of test protocols prerequisite to sale presupposes
that other requirements for CE marking, including construction and assembly
requirements established by the Low Voltage Directive [LVD] standards,
have been met.)
The consequences and costs of a failure at such a late stage can, of
course, be significant not only in terms of the time and money that
will be spent investigating the cause of failure but also measured as
potential disruption of the production process, loss of output, and
impact on profitability.
Immediate production problems and the sacrifice of profit margin to
redesign expenses are important matters, and bad enough. But sometimes
device failure emerges over a longer term. Identifying the reasons for
failure too lateafter product releasecan often prove to
be more serious and costly.
For example, a live conductor with insufficient insulation might nevertheless
pass a final test if its isolation due to clearance is sufficient to
allow it to pass the high-voltage stress test at final quality control.
However, this design or assembly defect could, during use by the customer,
present a potentially lethal problem that may become apparent only after
years of service.
The confusion between a protective ground (earth) and functional grounding
is a source of errors in design and assembly that might only come to
light if there is testing during the construction process. Such problems
can go undetected at the final test stage and subsequently present a
long-term safety hazard in the field.
Problems like these can be identified and eliminated at an early project
stage through the performance of testing at strategic steps in the assembly
process. A well-planned and well-managed safety testing policy implemented
throughout the manufacturing process need not involve undue complication
and expense. And there can be no better plan than to ensure that safety
and quality are inherent in the product during the design and assembly
stages.
This article discusses the four fundamental electrical safety tests
that designers of electrical products should employ during the product-building
process in order to design safety into any device. It relates specifically
to products covered by the LVD, those designed for use at a rated voltage
of 501000 V ac and 751500 V dc and intended to be marketed
in the EU. The focus should not obscure the fact that all the tests
named in the relevant harmonized standards are important unless they
are found to be inapplicable. Nor should it be interpreted to slight
requirements to determine the levels of other risks presented by an
LVD product, including mechanical risks and the danger of fire, explosion,
burns, and other potential causes of death or injury.
|
Inadequate Clearance Distances for Connectors
|
Clearance distances within device assemblies may have been
reduced as a consequence of postdesign changes adopted for reasons
unrelated to product safety, for example, to streamline a production
process. Unsatisfactory clearance may be attributable to a different
placement of components or to the unavailability at build of
the style of component envisioned during product design and
substitution with a physically different part. A placement-related
problem is illustrated in Figure 1a. In some cases, a problem
like this might be identified only by safety testing performed
during the production stage.
Another possibility is that an inappropriate fitting of connectors
has produced a clearance distance that is unacceptably small.
An example of this sort of problem appears in Figure 1b. Diagram
1 shows what could happen if individual connectors were used
to fit connection pins in close proximity. An adequate clearance
distance (X) at the point of connection is reduced to a dimension
(Y) below the required minimum at the point where the incorrectly
applied, unrestrained individual connectors approach each other.
In a situation like this, a successful test result would depend
heavily on stringent quality control.
Diagram 2 shows the effect of fixing the connectors in alignment
by attaching them to an insulator. The adequate dimension at
X now remains the clearance distance for the assembly at Y.
This illustration makes clear the advantage of using preformed
plugs and sockets.
|
|
|
|
Figure 1. Inadequate clearance distances.
|
Meeting the Standard
From the outset of the design process for any new electrical product,
the principal objective of the designer, with respect to the product's
electrical safety, must be to ensure that the correct level of protection
against electric shock is incorporated into the design. This involves
considering protection for both the person who has to build the product
and the eventual end-user. The environment in which the product is to
be used, the users' technical ability, the materials from which the
product is fabricated, and the technical specifications required by
relevant standards, directives, and legislation are all factors that
need to be taken into account. A similar process must be followed for
mechancial and other concerns.
At least one relevant standard applies to nearly every electrical product,
whether it be issued at a national, European, or international level.
Standards offer not only guidance regarding the design and construction
of specific types of products but also advise about the electrical safety
tests to be performed, as well as other tests such as those for temperature
rise and short circuit and overload. Care should be taken that tests
required during the design stages not be confused with those used in
the manufacturing process, as they do differ.
The central precompliance electrical safety tests that electrical product
designers should consider are ground testing (earth bonding), dielectric
strength (flash or hipot) testing, insulation resistance testing, and
ground (earth) leakage testing. The test procedures to be applied are
usually specified in the particular standard relevant to the product
under design and to the type of protection it provides under its classification
as Class I or Class II equipment.
Class I equipment or products are defined as those having protection
against electric shock not solely reliant on basic insulation, but rather
having all external conductive parts referenced to the ground of the
fixed wiring installation. In the event of breakdown of the insulation,
the user is protected by the grounding of the equipment or product.
Class II equipment or products incorporate two layers of insulation
that provide the user with sufficient protection from electric shock,
and they do not rely on a ground reference.
Designers of electrical products can conform to LVD requirements by
referring to a number of harmonized European standards for guidance
and for references to design principles and electrical safety testing
values. These product safety standards include:
-
EN 60335: Safety of household and of similar electrical appliances.
-
EN 60204: Safety of machinery.
-
EN 50144: Safety of handheld electrical tools.
-
EN 60950: Safety of information technology equipment.
-
EN 60065: Safety of household electronic appliances.
-
EN 60598: Luminaries.
-
EN 61010: Safety requirements for electrical equipment for measurement,
control, and laboratory use.
The ground bond test performs a measurement of resistance to determine
if the equipment would remain safe in the event that internal live conductors
touch the case. The test ensures that sufficient current will flow through
ground to blow the protective fuse in the plugtop or circuit breaker.
It uses a high current from a low-voltage test to make sure that ground
connections are correctly made. A failure indicates loose or poor ground
paths. The ground bond test applies to Class I equipment only; it cannot
be used on Class II equipment in which protection is supplied by double
insulation.
This test is designed to ensure the safety of the product. Thus, it
is seen as the first test to carry out, having priority over such tests
as those for dielectric strength or insulation resistance. Both recent
legislation such as the LVD and issues involving product liability have
made it more necessary for manufacturers to illustrate due diligence.
In addition, the trend toward using ground bond techniques to deal with
issues of electromagnetic compatibility, particularly conducted emissions,
means that the quality of the ground path becomes a matter of pertinence
to product performance as well.
To perform the ground bond test, a low voltage of less than 12 V (for
operator safety) is introduced to the input ground connection, which
often includes the supply cable. A measurement is then taken using a
clip or probe connected to each separate external metal surface. The
test is performed without the equipment connected to line voltage (a
mains supply). Rather, the connection is made with the power input lead
to be used with the equipment. Test current varies between standards,
although generally 25 A ac is used. Exceptional examples include lighting
fixtures, which require a test at 10 A ac, and machinery under the the
Machinery Directive standard EN 60204, which requires a constant current
of 10 A ac, after which the voltage drop is measured. The permissible
drop is determined by the cross-sectional area of the grounding conductor.
The pass-fail limit for the ground bond test measurement of resistance
also varies between standards. In general, a test at 25 A requires a
resistance of 0.1 W. Lighting equipment tested
to EN 60598-1 using 10 A has a pass-fail threshold of 0.5 W.
Ground bond tests should not be confused with ground leakage. Ground
bond ensures a sound connection of the metal case to the power-line
(mains) ground reference, whereas ground leakage monitors the leakage
from the ground to live and neutral conductors at normal supply voltage
(230 V). Thus, good ground bonding is a prerequisite to dealing with
the presence of ground leakage.
Sensitive electronic equipment calls for special test considerations.
A common design feature of personal computers, for example, is that
they have secondary, or peripheral, grounding points after the primary
grounding position, which can use PCB tracks. Care has to be taken not
to apply the high test current to these points, as damage may be caused.
The only way to avoid this problem is through visual identification
of the primary ground. This requires a combination of training and the
foresight to label or indicate the correct test point clearly.
Some equipment has grounding points that are difficult to access. For
example, the element in an electric kettle is the only grounded component.
Other devices have grounding points that are hard to access because
of plastic shrouds. These difficulties sometimes must be addressed during
the product design stage so that proper consideration is given to the
positioning of ground test points and so that the test process requirements
of production testing are taken into account.
To accommodate all possible design-related causes of failure, the ground
bond test should include the power input lead. Since the ground bond
measurement of resistance is dependent on the length of the conductor
as well as its cross-sectional area, an unnecessarily long power supply
lead may give a failure reading. Leads of 23 m will not cause
any problems for achieving the normal pass-fail criteria, but some products,
such as floor cleaners, that require much longer supply leads owing
to the nature of their use will require careful assessment of their
test results. Thus, attention should be paid to the length of lead supplied.
It is also important to consider how manufacturing tolerances in production
may invalidate assumptions made for the product as designed. For example,
joints that rely on compression may not seal as completely as anticipated
during the design phase, and hinges may not provide the degree of continuity
that was originally expected. Faults like these can result in product
assemblies that have no effective reference and that therefore present
a potential electric shock hazard and noncompliance with requirements
of the LVD.
|
The Safety Ground Terminal
|
| The safety ground terminal on Class I electrical equipment must
be a dedicated terminal not used for any other purpose. Were it
to be used for fixing components such as transformers or circuit
boards to the case, and if such components were disturbed during
maintenance, modification, or other activity, the ground integrity
of the case could be inadvertently and unknowingly compromised.
Testing and inspection of this important terminal during the production
process can expose any problems at an early stage. A suggested method
of construction is presented in Figure 2. |
|
|
|
Figure 2. Safety ground terminal.
|
Dielectric Strength Testing
Dielectric strength testing does not in fact involve a measurement
but rather is a procedure that aims to illustrate whether a product
remains safe when subjected to a high voltage. The test is designed
to determine if gaps or clearances between conductive parts and a ground
are sufficient and if degradation, such as pinholes and cracks in insulation
or other protective devices, has occurred as a result of production
processes or other sources of wear and tear. High voltage is applied
to the product to test the insulation between live conductors and all
exposed metal surfaces. For Class I equipment, the high voltage is applied
between the conductors and a ground. For Class II equipment, the application
point is between the conductors and the outer surface of the product.
Voltage levels applied vary by product type in accordance with the
relevant product-specific standards, but Class I equipment items normally
require between 1000 and 1500 V applied for 1 minute with a trip level
of 0100 mA, depending on the relevant product standard. Voltages
for Class II equipment are usually higher, between 2500 and 4200 V,
but the time and trip settings are similar.
Production-line dielectric testing calls for special considerations
because certain practicalities affect the voltage levels and duration
of application. These tests need to be faster and yet be equally rigorous.
In general, a 10% overvoltage is applied during a test time of a few
seconds. Thus, a type test with a voltage rating of 1250 V would be
carried out on the production line at 1375 V with a trip level of 5
mA.
Note that it is possible to get an apparently satisfactory test result
when in fact the equipment is switched off or not properly connected.
Obviously, the equipment under test must be checked to ensure that it
is switched on and connected appropriately. This circumstance can be
a stumbling block even for experienced test operators.
In Class II equipment, the absence of a ground makes protection via
primary and secondary insulation necessary. A common test problem, particularly
with new equipment, is that a failure occurring on the primary insulation
is undetectable by a dielectric test on the outer surface, which checks
the secondary insulation only. All testing regimes should include tests
of both these levels.
To test the primary level of protection, a method of gaining access
to the primary insulation must be available. This is somewhat paradoxical,
since this connection needs to be an inaccessible conductor. However,
experience has shown several options to be feasible. First, the primary
insulation can be tested prior to the final assembly of the device.
The important concomitant here is that checking should be done upon
assembly to determine that no degradation of this level of protection
has taken place, such as screws penetrating the insulation. A second
alternative is to design the product with an access point that can be
permanently sealed after testing. Product designers do not often foresee
this need. Another possibility is to design test jigs and probes that
afford access through the enclosure while ensuring that the integrity
of the product in terms of the relevant standard finger tests is maintained.
Testing of the secondary protection also needs to be carried out. Standards
generally specify that the device under test be wrapped in aluminum
foil so that high voltages can be applied to all the outer surfaces.
Such a test may be practical for the laboratory environment, but it
is impractical in production scenarios, both because of the complexity
of test setup and the time required and because the outer surfaces of
the product can easily be marked. The use of conductive foam in a special
jig to create a nest or envelope around the product enables test voltages
to be applied to the subject without marring its finish. Although not
quoted in standards, this methodology devised by Clare Instruments (Worthing,
W Sussex, UK) is recommended by standard authorities.
Concerns have also been raised that ac dielectric testing could corrupt
sensitive electronic components. A possible solution is to use a dc
dielectric test. The voltage applied needs to match the specified peak
ac voltage; this is calculated by multiplying the specified ac voltage
by 1.414. A discharge facility to ensure that no residual voltage remains
following application is required.
Another available dc dielectric test, known as the soft dc test, involves
ramping up to the required voltage. In some instances, this test can
benefit from ramping down as well. The complete test would consist of
a slow ramp from zero up to the required value, which is then held for
a timed period before ramping back down to zero and discharging the
unit under test.
|
Correcting Ground Bond Test Failures
|
Because ground bond test results should be very low measurements
of impedance, an unsatisfactory test outcome is not uncommon.
However, satisfactory retests are relatively simple to achieve
if the fault is detected during the assembly phase of production.
Following are three situations that can result in ground bond
test failure and the solutions for converting a fail to a
pass.
Problem: The test probes are not making a good contact with
the product's conductive metalwork and the meter terminals
because of a decorative or protective coating. Although such
coatings as paint or anodizing must not be considered as insulation
for purposes of construction, they will present a high impedance
to the test current if they are not penetrated by the probes
for the test process.
Solution: Make the connections again with penetration and
retest.
Problem: Parts of the equipment case have been assembled
after a decorative or protective coating has been applied.
In such a situation, ground continuity will be fortuitous;
that is, it will only occur where, by chance, the edge of
a fixing screw happens to touch the edge of the cover fixing
hole as illustrated in Figure 3.
Solution: Change the surface-finishing process by masking
the required ground continuity arrangements before the coating
is applied, use a penetrative star-type washer for intentional
grounding, or reorder the sequence of manufacturing processes.
Problem: The ground conductor between the equipment ground
input pin and the safety ground terminal does not have at
least the same cross-sectional area as the circuit-protective
conductor within a correctly rated flexible cord.
Solution: Replace the conductor with one of adequate size.
|
|
|
|
Figure 3. Ground bond test failure.
|
Insulation Resistance Testing
The insulation test acquires a measurement in megohms of the resistance
of a product's insulation protection by applying a dc voltage between
the phase (live) and neutral conductors to the ground conductor for
Class I equipment and between the phase and neutral conductors to the
outer case for Class II equipment. The test is designed to ensure that
protective insulation forms a barrier sufficient to prevent electricity
from coming into contact with a user so as to cause injury, or to prevent
other systems in the vicinity from being adversely affected. Legislation
such as the LVD requires evidence of due diligence in the production
environment. Results of the insulation and other tests can be used to
fulfill this requirement.
The insulation resistance test can be applied to both Class I and Class
II equipment. It is carried out with the use of probes or insulated
clips, without the equipment being connected to a power supply. Test
voltages vary between standards; the most common application called
for is 500 V. The voltage is applied for 2 to 3 seconds. In general,
Class I equipment must display a resistance greater than 2 MW
to pass the test. Resistance greater than 7 MW
is required for Class II equipment. Both classes call for a 5 or 10%
accuracy, with specific exceptions.
Equipment has been designed to supply up to 1000 V for testing such
devices as automobile ignitions that call for greater levels of protection.
Equipment is also available with voltages as low as 100 V to test switches
and other devices that might be damaged by higher voltages.
Insulation resistance testing is designed to provide a quantitative
representation of the quality of insulation. If a wire was positioned
0.5 mm from exposed metal, an insulation testconducted in dry
aircould well provide a pass reading. A dielectric test would
be more likely to reveal the danger in this situation. Similarly, if
insulation is somehow contaminated, a dielectric strength test would
result in a pass but an insulation test would highlight the deficiency.
For example, the normal minimum insulation resistance value for Class
I appliances is 2 MW; with a 1500-V dielectric
test, the current would be 0.75 mA and would not be detected by the
5-mA trip that has to accommodate the capacitive losses that occur.
Obviously, a dc dielectric test with a leakage meter can provide insulation
resistance monitoring, as the capacitive component is overlooked after
the initial inrush.
The ground leakage test is the most misunderstood safety test. It was
devised to provide some measure of the quality of the insulation resistance
at line voltage potential when it is inappropriate or impossible to
perform dielectric strength or insulation resistance tests.
In any domestic or industrial power supply, a substantial current normally
flows from the live conductor through the various loadsmotors,
heating elements, and so onand returns to the neutral conductor.
This current then flows, via the neutral conductor, to the local substation
where it is bonded to true earth. This is literally the "ground," or
planet Earth. To provide protection and screening from the live and
neutral conductors, a third conductor, ground, is included.
In a perfect world where conductors had no resistance and insulators
had infinite resistance, the current drawn by an appliance would remain
in the live-to-neutral loop, and no current would flow in the ground
conductor. However, in the real world, the current in the live conductor
can leak, via insulation, to any other conductor. The neutral conductor
can also become elevated to 40 V above true earth, so current can also
leak from this conductor. The net result is that these leakage currents
flow back to true earth via the ground conductorhence the term
ground leakage.
If the ground conductor in a Class I appliance were to become disconnected,
then this leakage current, or part of it, would flow via the lowest-impedance
path to true earth. Unfortunately, this could be the person holding
or touching the appliance if that individual were in direct contact
with the ground.
Class II appliances have no grounding wire; their leakage current would
normally flow to true earth via the neutral conductor. In this case,
if the neutral conductor were to become disconnected, the leakage current
would again take the lowest-impedance path to true earth, which again
could be a person in contact with both the appliance and the ground.
Measurement of ground leakage in an electrical appliance can be performed
by two distinct methods, both of which are conducted with the product
powered up. Care must be taken that no hazard to operators can arise
from moving parts or heating elements.
The first test method involves the insertion of a sensitive current-measuring
device directly between the ground wire of the appliance and the supply
ground. A reading of the current flow in the ground path is taken with
the appliance turned on. The power connections are then reversed and
a second reading taken, which takes into account a possible polarity
reversal in manufacture or installation. In some instances, the impedance
of the measuring circuit is designed to replicate the impedance of the
human body.
For Class II appliances in which there is no ground wire, the measurement
is taken between the outer surface of the appliance, wrapped in conductive
foil, and true earth. This particular method can be hazardous and must
only be undertaken by skilled personnel under strictly controlledusually
laboratoryconditions.
The second method uses current transformers and Hall-effect devices,
which do not require the disconnection of the ground conductor. Ground
leakage current in Class I appliances can be directly monitored via
this method. Because this method is less hazardous, it is often preferred
in the production environment.
Class II appliances might have the measurement taken as with the first
method or a different way, specific to this second method. The alternative
involves taking a differential measurement: the difference between the
measured current flows in the line and neutral wires is taken to be
the ground leakage (i.e., line current neutral current = ground
current).
Permissible levels of ground leakage current vary among product types
and related standards. The selection of values presented in Table I
gives an indication of the range.
|
Product Type
|
Class I
|
Class II
|
| Household appliances |
0.75
|
0.25
|
| Cookers |
0.75 per kilowatt of
load (5 maximum)
|
N/A
|
| Lighting appliances |
1.00
|
0.50
|
| Handheld tools and portable appliances |
0.75
|
0.25
|
| Information technology |
0.75
|
0.25
|
| Information technology, stationary |
3.50
|
N/A
|
| Table I. Permissible levels of ground leakage current,
in milliamperes, specified for selected product types in European
product safety standards. N/A = not applicable. |
Conclusion
The precompliance tests described above, performed with in-house instruments
by operators knowledgeable about the role and limitations of each procedure,
are invaluable tools to apply during the design and assembly phases
of electrical product manufacture. Used in a timely manner, they can
help ensure that user safety is an integral component of the final product
design.
Clearly, the extent and severity of testing will vary from product
to product. Test conditions may necessitate modifications of the working
environment for the protection of assembly or test personnel. (EN 50191
is a good guide for the erection and operation of test equipment both
within and outside the EU.)
There can be no doubt that an investment in test instrumentation and
in the time required for effective electrical safety testing to be carried
out during the product-building process will be repaid many times over
if the potential for a product to be dangerous or susceptible to damage
is eliminated and if product recalls can be avoided.
|