| EMC Testing and Design: The Impact of Emerging European
Standards
Jerry Ramie
Understanding and incorporating the latest standards into early testing
and design is key to market success.
Most major electronics manufacturers are concerned with the marketing
of consumer, commercial, medical, or light industrial products in the
European Union (EU). To apply the CE mark, the EU's new approach directives
mandate new and expanded requirements for regulatory compliance for most
electrical and electronic products.
To meet these requirements, the EMC Directive (89/336EEC) references
harmonized EMC standards. The newest versions of many of these standards,
coming into effect in 2001, affect a vast array of products, most of which
will have a much-increased number of tests applied. This article examines
these emerging standards and their implications for manufacturers.
New harmonized standards or new versions of harmonized standards being
referenced this year include:
- EN 50082-1:1997 Generic Immunity Standard for Residential, Commercial,
and Light Industrial Locations (7/1/01).
- EN 50130-4:1995 Immunity Requirements for Components of Fire, Intruder,
and Social Alarm Systems (1/1/01).
- EN 55011:1998 Emissions Tests for Industrial, Scientific, and Medical
(ISM) Equipment (1/1/01).
- EN 55022:1998 Information Technology Equipment (ITE) Emissions Testing
Requirements (delayed until 8/1/03).
- EN 55024:1998 (ITE) Immunity Testing Requirements (7/1/01).
- EN 61000-3-2:1995 Power-Line Harmonics (1/1/01) + Amendment A14 (optional
from 1/1/01).
- EN 61000-3-3:1995 Power-Line Flicker (1/1/01).
- EN 61326-1:1997+A1 (1998) Emissions and Immunity for Equipment for
Measurement Control and Laboratory Use (7/1/01).
These new standards (or new versions) add a number of tests that
have never before been required by most EMC Directive harmonized standards,
including:
- Emissions of power-line harmonic currents (in EN 61000-3-2:1995).
- Emissions of power-line voltage fluctuations and flicker (in EN 61000-3-3:1995).
- Conducted emissions on telecom ports (only for ITE, in EN 55022:1998).
- Radiated RF immunity using modulated fields (basic test standard IEC
61000-4-3).
- Surge immunity (basic test standard IEC 61000-4-5).
- Conducted RF immunity (basic test standard IEC 61000-4-6).
- Power-frequency magnetic fields (basic test standard IEC 61000-4-8).
- Power dips and interruptions (basic test standard IEC 61000-4-11).
An understanding of the requirements imposed by conformity to these
standards is essential. It is important to incorporate these requirements
in test plans at the design stage to ensure that new products conform
to recently mandated tests. Failure to grasp the implications these
new and updated standards have on products can impede access to critical
markets.
Background
Currently, products bound for the EU must conform to the essential
requirements of the EMC Directive. Table I shows the harmonized standards
for emissions, and Table II shows those for immunity. For regulatory
compliance testing, most manufacturers want to design products so
that they comply with standards for both Europe and the United States.
Therefore, to combine tests, radiated emissions are now typically
tested in accordance with CISPR 16-1:1993 methods, but using the frequency
ranges specified in 47 CFR 15.33 (FCC). Many commercial manufacturers
now test for combined radiated emissions from 30 MHz to 5 GHz, reflecting
the FCC guidelines. Some telecommunications equipment manufacturers
test up to 10 GHz, using GR-1089-CORE for guidance.
|
Type of EM
Disturbance
|
New or Revised
Harmonized EMC Standards with a Date of Withdrawal During 2001 |
Basic Test Method
Called Up by the Harmonized Standard |
|
Radiated
|
EN 55022:1998 (delayed) |
The method is in the standard. |
| EN 55011:1998 |
The method is in the standard. |
| EN 61326-1:1998 |
CISPR 16-1 and -2 |
|
Conducted on mains ports
|
EN 55022:1998 (delayed) |
The method is in the standard. |
| EN 55011:1998 |
The method is in the standard. |
| EN 61326-1:1998 |
CISPR 16-1 and -2 |
|
Conducted on telecom ports
|
EN 55022:1998 (delayed) |
The method is in the standard. |
|
Mains harmonics
|
EN 61000-3-2:1995
(Amendment A14 optional)
|
The method is in the standard. |
|
Mains voltage flicker and in-rushcurrent
at switch-on
|
EN 61000-3-3:1995 |
The method is in the standard. |
Table I. This table indicates the major harmonized standards for emissions.
These harmonized standards then call up some of the basic (utility)
standards.
|
Type of EM
Disturbance
|
New or Revised
Harmonized EMC Standards with a Date of Withdrawal During 2001
|
Basic Test
Method Called Up by the Harmonized Standard
|
|
Radiated RF (modulated field)
|
EN 55024:1998
|
All EN 61000-4-3; Note: Uses
modulated RF fields unlike the IEC 801-3 unmodulated fields
employed by EN 50082-1:1992
|
|
EN 61326-1:1998
|
|
EN 50130-4:1996
|
|
EN 50082-1:1997
|
|
Conducted RF (modulated field)
|
EN 55024:1998
|
All EN 61000-4-6
|
|
EN 61326-1:1998
|
|
EN 50130-4:1996
|
|
EN 50082-1:1997
|
|
Electrostatic discharge wave
|
EN 55024:1998
|
EN 55024:1998 All EN 61000-4-2;
Note: Uses a faster wave shape, ± test voltages, and adds
contact discharge and indirect discharge tests to the IEC 801-2
method employed by EN 50082-1:1992
|
|
EN 61326-1:1998
|
|
EN 50130-4:1996
|
|
EN 50082-1:1997
|
|
Fast transient bursts
|
EN 55024:1998
|
EN 55024:1998 All EN 61000-4-4;
Note: Essentially the same as IEC 801-4 employed by EN 50082-1:1992
|
|
EN 61326-1:1998
|
|
EN 50130-4:1996
|
|
EN 50082-1:1997
|
|
Surge
|
EN 55024:1998
|
All EN 61000-4-5
|
|
EN 61326-1:1998
|
|
EN 50130-4:1996
|
|
EN 50082-1:1997
|
|
Power frequency magnetic field
|
EN 55024:1998
|
All EN 61000-4-8
|
|
EN 61326-1:1998
|
|
EN 50130-4:1996
|
|
EN 50082-1:1997
|
|
Supply dips, interruptions,
and variations
|
EN 55024:1998
|
All EN 61000-4-11
|
|
EN 61326-1:1998
|
|
EN 50130-4:1996
|
Table II. This table indicates the major new or
revised harmonized standards for immunity. The standards call up a
selection of the basic test standards in the IEC/EN 61000-4-x series.
Compliance to the EMC Directive cannot be declared using the IEC/EN
61000-4-x series of basic test standards. Rather, product standards
or generic standards, which are harmonized, must be used.
Performance Criteria
When performing immunity (susceptibility) testing on actual products,
the definition of a failure becomes important. To ensure consistency
in this regard, performance criteria are stated as:
- Type A: Performance during the test does not fall below a level set
by manufacturer (usually normal specification).
- Type B: Performance is normal after the test, with no loss of stored
data or change in operational mode. Performance degradation is allowed
during the test.
- Type C: A and B criteria apply, but normal performance after the test
requires operator intervention using normal controls.
- Type D: Nonrecovering failure (damage).
IEC 61000-4-5 (1995-02)
This standard requires the coupling of the widely used combination
wave onto the power lines, and sometimes onto the input/output (I/O)
lines of electrical and electronic equipment connected to the ac power
distribution system. The test severity level and coupling type are
governed by the generic or product harmonized standard that applies
to the product. The level and coupling type are generally dictated
by the installation class of the product being tested. Many commercial
products fall within Class 2 or Class 3 (without cabling runs outside
the building). These products may be subjected to power line and unbalanced
I/O surges of 0.5 or 1 kV, line-to-line, and 1 or 2 kV, line-to-earth.
If a product has an unbalanced long-distance bus (>3 m long) or
a balanced circuit, it can also be tested with 1 or 2 kV, line-to-earth.
It is important to refer to the product or generic standard or to
Annex A and Table A.1 in IEC 61000-4-5 (1995-02) for guidance on choosing
the correct installation class and identifying proper test levels
and coupling methods.
IEC 61000-4-6 (1996-04)
Nearly all products have wires for power or I/O interfacing, and
these lines are exposed to continuous sources of radio- frequency
(RF) interference. Licensed radio and TV stations, land and air mobile
services, cellular telephony, local-area network (LAN), and wide-area
network systems are all subject to RF voltages induced onto their
lines and must address concerns about immunity. To simulate the effect
these phenomena can exert, this conducted immunity standard requires
testing at 1, 3, or 10 V electromagnetic force (EMF). The test level
is determined by the harmonized standard that applies to the product.
Many commercial products can be tested at Level 2 (3 V EMF) or Level
3 (10 V EMF) using a coupler-decoupler network (CDN) on the power
lines and on other common types of I/O lines such as coaxial, twisted
pair, audio, D-sub-9 and D-sub-15.
|
|
|
Figure 1. A level-setting
procedure conducted on the mains 3-wire coupler-decoupler network.
|
Before the test can be run, IEC 61000-4-6 stipulates a level-setting
procedure. The control computer (or pencil-wielding technician) makes
a drive table consisting of the frequency (in 1% steps) and the signal-generator
output level (in dBm). The output of the signal generator is adjusted
to achieve the desired reading on the power meter or oscilloscope. The
photograph in Figure 1 shows the level-setting procedure being conducted
on the mains 3-wire (M3) CDN, the most common type used for power lines.
Note that each side of the CDN must be fitted with an appropriate calibration
adapter to establish the common-mode reference point 30 mm from the
CDN and 30 mm above the ground plane. These adapters are removed after
the level-setting procedure, and the drive table is then played back
with a dwell time at each frequency long enough for the equipment under
test (EUT) to respond. During the test, the EUT is monitored for its
functional performance.
For some high-speed I/O lines (10/100Base-T or higher), CDNs will
not allow the line to function when it is connected. In these cases,
one of two clamp-injection techniques can be used. An electromagnetic
clamp offers front-to-back isolation from its ferrite decoupling section,
but at a higher cost than a bulk current injection (BCI) probe. Most
test laboratories worldwide have BCI probes available because these
probes are widely used in MIL-STD work. Both methods require monitoring
of the injected current to ensure that the EUT is not overtested.
Both methods also require that the auxiliary equipment (AE) side of
the clamp be decoupled with a separate ferrite decoupler. All lines
touching either the EUT or AE sides of the setup must be decoupled
with additional CDNs or ferrite decouplers.
IEC 61000-4-8 (2001-03)
Most commercial products available today are connected to or used
near a low-voltage (LV) ac power distribution network. These products
are subjected to 50-Hz magnetic fields relating to their proximity
to nearby transformers and distribution panels. IEC 61000-4-8 differentiates
between long-term, steady magnetic fields and short-term (and much
higher) fault-condition magnetic fields. Levels are determined by
the appropriate harmonized standard. Typical commercial products can
be tested to Level 2 (3 A/m) or Level 3 (10 A/m) for continuous fields.
Many products can be tested within the 1-m-sq induction coil by
the immersion method. A single-turn coil of this dimension yields
a 3-dB uniform magnetic field for products up to 0.6 x 0.6 x 0.5 m
tall. If two coils are connected in series and separated by 0.8 m,
the resultant solenoid will yield a uniform field for EUT sizes up
to 0.6 x 0.6 x 1.0 m tall. Larger floor-standing EUTs may require
custom coils that return current through a ground plane so that the
uniform field extends down to the plane.
All setups for IEC 61000-4-8 (2001-03) require a small, three-axis
magnetometer to verify the field strength in the center of the coil.
Many of these meters are calibrated in microteslas, with 1.26 mT =
1 A/m.
IEC 61000-4-11 (2001-03)
Many believe that harmonic distortion is the greatest power problem
we face. However, according to Robert Gilleskie of San Diego Gas &
Electric Company, "Very brief voltage sags, some down to only 90%
of nominal, and lasting as little as a tenth of a second, are by far
the more troublesome."1 For electrical and electronic equipment
connected to the low-voltage mains, IEC 61000-4-11 defines the immunity
test methods and levels for voltage dips, short interruptions, and
voltage variations. This standard applies to electrical and electronic
equipment with rated input currents of 16 A per phase, single or three
phase. (It excludes dc and 400-Hz networks.) Voltage dips and interruptions
are caused either by faults in the network or installation, or by
sudden, large changes in load. These phenomena are random and not
always abrupt. Voltage dips simulate the effects of sudden voltage
change; however, rotating machines can act as generators when spinning
down, preventing rapid voltage changes in some installations. Hence,
the voltage variation tests require gradual changes in voltage.
When following the standards route to compliance, the test levels
applied are set by the generic or product harmonized standard. Voltage
dips (short interruptions) may be delivered with sags down to 0, 40,
and 70% of nominal rated voltage, with durations from 0.5 periods
(cycles) to 50 periods (1 second at 50 Hz). The EUT can be subjected
to combinations of test levels and durations with a series of three
dips separated by a minimum of 10 seconds, as determined by the appropriate
standard. These interruptions occur at the zero crossings for most
tests, but other phase angles could be imposed if considered critical.
The test generator must be able to deliver 1.4 times the actual
in-rush demanded from the EUT, or 500 A maximum. The EUT must not
draw more than 70% of the actual in-rush capability of the test generator,
which must be capable of an output current of 16 A rms per phase at
rated voltage. The generator should supply the following voltages
and currents for at least 5 seconds:
- Voltage change at 100% output (016 A) < 5%.
- Voltage change at 70% output (023 A) < 7%.
- Voltage change at 40% output (040 A) < 10%.
- Abrupt load-change rise (fall) time (100-W load): 15 ms.
The standard shows a dual-transformer circuit with solid-state switching
as representative of this type of test generator. Such a circuit could
switch at any phase angle and not limit the in-rush current or the
output bandwidth. The generator's implied bandwidth from the load-change
validation test is 200 kHz1 MHz, precluding the use of any stand-alone
programmable electronic ac power source for this type of generator.
Usually, a dual-transformer source controller is connected in series
with the output of an appropriate 50-Hz power source, and this controller
sets the output voltages and durations according to the standard.
If required under the harmonized standard, the optional voltage
variation part of the standard requires that the generator supply
nominal rated voltage to the EUT, then execute a 2-second linear ramp
down to 40% (or 0%) of rated voltage, hold at the reduced voltage
for 1 second, then ramp back up to nominal voltage. This series is
repeated three times with a minimum 10-second interval between events.
The EUT should remain safe during and after the completion of the
test.
EN 61000-3-2:1995
This standard applies to electrical and electronic equipment drawing
up to 16 A per phase from a public low-voltage distribution system.
With the increasing prevalence of electronic loads, the problems they
create are becoming more widespread. Most troublesome is the tendency
of low-order odd harmonics of an input current waveform to add in
three-phase wye distribution transformers, particularly in the neutral
line. High neutral harmonic currents can damage utility equipment,
interfere with accurate metering of power consumed, or even ignite
fires. The existing equipment classifications are:
- Class A: Balanced three-phase and all other equipment not classified
below.
- Class B: Portable tools.
- Class C: Lighting equipment and dimmers.
- Class D: Special wave-shape equipment.
On January 1, 2001, the Official Journal of the European Community
published amendment A14 to EN 61000-3-2:1995. A14 is optional for
the next three years, by which time the 1995 version should have been
withdrawn and replaced with a new standard incorporating the A14 modifications.
This amendment implemented several changes, including a new system
for equipment classification. Equipment classifications under Amendment
A14 are:
- Class A: Balanced three-phase, permanent tools, appliances, audio
equipment, incandescent-light dimmers, and all other equipment not classified
below.
- Class B: Portable tools.
- Class C: Lighting equipment (except incandescent dimmers).
- Class D: Computers, monitors, TV receivers (<600 W single phase).
Amendment A14 provides manufacturers some relief if their products
previously fell under the old Class D, special wave-shape equipment.
Before A14, manufacturers were required to meet both the absolute
and relative harmonic current limits. Many manufacturers can now retest
to Class A, which should be a much easier test to pass. For computer,
monitor, and TV manufacturers, however, this amendment does not offer
any relief. These products typically must be outfitted with power-factor-corrected
power supplies in order to pass the test.
Classifications and measurement methods outlined in A14 are easier
to understand and apply. Under A14, maximum total harmonic distortion
measurement speeds up testing, and limits apply to phase rather than
neutral currents.
Some manufacturers will not have to test to EN 61000-3-2 at all.
It does not apply to products that consume less than 75 W or to professional
equipment that draws more than 1000 W. An exception to the 75-W limit
is lighting equipment, for which the lower power limit is for Class
C only. A14 adds new harmonic requirements for lighting equipment
rated less than 25 W. Other products exempted from the limits of EN
61000-3-2:1995 include:
- Professional equipment (used by workers at work) drawing more than
1000 W.
- Equipment that consumes more than 16 A per phase or is powered from
medium-voltage (MV, above 1 kV rms) or high-voltage (above 32 kV rms)
lines.
- Equipment used on a site that has its own dedicated MV-to-LV transformer
(such as most high-rise buildings, hospitals, or factories) and not
intended to be connected to a public supply (public is defined
as shared between more than one organization or household).
- Professional equipment that doesn't meet the limits can still be supplied,
as long as the user seeks permission from the supply authority before
connecting. Supply authorities could require additional tests or improvements
to the customers' supply networks.
Despite these exemptions, equipment that falls within the scope
of EN 61000-3-2:1995 (with or without A14) must still be documented
on the declaration of conformity.
EN 61000-3-3:1995
When products are connected to the nonzero impedance of an ac mains
network, any variation in the amplitude of the current drawn will
result in a corresponding variation in the luminance of typical incandescent
lighting. This flickering of the lighting level is now regulated by
EN 61000-3-3:1995, and this standard applies to electrical and electronic
equipment drawing up to 16 A per phase from the public low-voltage
distribution system (220250 V ac, 50 Hz line-to-neutral) The
standard does not apply to equipment running on public LV supplies
of more than 250 V rms phase to neutral or on frequencies other than
50 Hz nominal. Short-term flicker (Pst)
is the flicker severity evaluated over a short period (about 10 minutes),
where Pst = 1 is the limit for human
irritability. Long-term flicker (Plt)
is the flicker severity evaluated over a long period (about 2 hours),
using successive Pst values. The simulated
power distribution network must be in accordance with IEC 60725 (1981-01).
To simulate the nonzero impedances of the phase and neutral lines,
the power source must exhibit these impedances:
ZA = 0.24 + j 0.15 W @ 50 Hz (phase)
ZN = 0.16 + j 0.10 W @ 50 Hz (neutral),
where j refers to inductive reactance.
A cautionary note: Many manufacturers (and test labs) have overlooked
the fact that EN 61000-3-3 applies limits to the switch-on in-rush
current, which means that most equipment must be tested, if only for
switch-on. If possible, specific test conditions outlined in the standard
should be used for:
- Cookers
- Hot plates
- Baking ovens
- Grills
- Combined oven/grills
- Microwave ovens
- Lighting equipment
- Washing machines
- Clothes dryers
- Refrigerators
- Copiers, laser printers
- Vacuum cleaners
- Food mixers
- Portable tools
- Hair dryers
- Consumer electronics
- Water heaters
EN 61000-3-3 also allows some exemptions, basically as for EN 61000-3-2,
but without the 75-W cutoff or the exemption for professional equipment
consuming over 1 kW.
EN 55022:1998
Computers and telecommunications equipment are subject to testing
in accordance with EN 55022:1998 as of August 1, 2003. As with the
former standard, EN 55022:1995, the new version requires radiated
emissions testing to 1 GHz, independent of internal clock speeds.
EN 55022 does not require testing to 10 GHz. However, many manufacturers
that use this method should extend the frequency range to 5 or 10
GHz to meet FCC or GR-1089-CORE clock-related frequency limits. This
standard has been delayed, and ongoing work is being done to clarify
the test methods required, especially the calibration of the impedance
stabilization networks (ISNs).2 The EMC Test Labs Association
has published a guidance document.3
|
|
|
Figure 2. Conducted common-mode
disturbance at telecommunications ports (Class A and B).
|
As before, line impedance stabilization networks are used for conducted
emissions testing on the power lines of the EUT. The major difference
in the new version is the requirement that ISNs are to be used on telecom
ports to set their common-mode impedance to 150 W. The standard
defines a telecom port as any analog or digital lines connecting to
the telecom network, including LAN or coaxial ports. A new conducted-emissions
common-mode current or voltage limit (ranging from 150 kHz to 30 MHz)
is placed on these lines. The Class A and B limits are shown in Figure
2.
If possible, single- and twin-pair cables should be connected through
the ISN specified in section 9.5.2-C1. CAT-3 and CAT-5 cables are
routed through the ISNs specified in sections 9.5.2-C2 and -C3. Compliance
with the common-mode current or voltage limit is required, and multiple-pair
bundles must conform to common-mode voltage and current limits. The
common-mode voltage is measured using a capacitive voltage-probing
fixture, and the common-mode currents are measured with a traditional
monitor current probe. The common-mode impedance of the bundle must
be controlled with suitable ferrites and verified with an injection-
and monitor-current probe pair.
For coaxial cable, Figure C.1 of the standard allows the use of
the S-1 CDN called for in IEC 61000-4-6 (1996-04), so many companies
are likely to have one for meeting the requirements of that standard.
In this case, a monitor current probe should be used to measure the
common-mode currents. If the current measurement is beyond the limit,
however, a voltage measurement is allowed. A 50150-W adapter
as called for in IEC 61000-4-6 (1996-04) can be used (with a correction
of 9.6 dB) as shown in C.1.2 to measure common-mode voltage on the
shield.
Other Standards
Other standards issued recently, including EN 55011:1998, EN 55024:1998,
and EN 61326-1:1997, address the important markets of the industrial,
scientific, medical, information technology, and measurement and control
industries. EN 51030-4:1997 addresses immunity for fire, intruder,
and alarm systems. These standards reference many of the basic standards
mentioned and should be consulted for guidance for the testing requirements
of a particular product covered within their scope.
It is important to note that the new 1997 edition of the generic
immunity standard EN 50082-1 has changed its test method for measuring
radiated immunity. Instead of using the unmodulated-field test that
EN 50082-1:1992 used to specify (using IEC 801-3 for the basic test
standard), EN 50082-1:1997 now specifies a modulated field (using
EN 61000-4-3 for the basic test standard). The modulated field increases
the effective peak test level by almost 6 dB. This is especially bad
news for analog circuits and other devices that tend to demodulate
the modulation. From 2001, many products for which EN 50082-1 continues
to apply could face serious problems passing the modulated-field radiated
immunity test in this new version of the generic immunity standard.
Another test that has become much tougher in the 1997 issue of EN
50082-1 is electrostatic discharge. The 1992 edition employed the
IEC 801-2 basic test method, whereas the 1997 issue uses IEC 61000-4-2
instead. This method uses a different human body model with a much
faster-rising leading edge to its waveform (between 0.7 and 1 nanosecond,
instead of 5 nanoseconds as in IEC 801-2). Faster rise times generally
mean more likelihood of interference occurring. In addition, IEC 61000-4-2
tests with both positive and negative voltages, with contact discharge
as well as the traditional air discharge. It also tests with indirect-contact
discharges to nearby horizontal and vertical reference planes.
Many products to which the generic standard EN 50082-1 used to apply,
but during 2001 must migrate to new product-specific harmonized immunity
standards (e.g., EN 55024, EN 61326-1, EN 50130-4), could also suffer
serious problems with the IEC 61000-4-3 modulated-field or IEC 61000-4-2
ESD tests, even if they had no problems with the corresponding tests
under EN 50082-1:1992.
Conclusion
With the EU representing one of the largest integrated, regulated
markets in the world and with continuing pressure on manufacturers
to get to all markets first with new products, the importance of a
regulatory strategy is greater than ever. Such a strategy might encompass
early adoption of good EMC engineering practices during the design
and product specification phase, with ongoing EMC validation at the
subassembly and finished-product stages. A single, high-quality design,
quickly placed on all markets, can often make the difference between
industry dominance and industry extermination.
The burdens for EMC testing (and early design validation) are not
impossible and, of course, apply to the competition as well. Meeting
the requirements set forth in international standards results in a
better-quality and more-reliable product. These testing standards
only impact time to market or windows of opportunity if they are ignored,
rather than managed. With so much at stake, a clear regulatory strategy
makes the most sense.
References
1. RJ Gilleskie et al, "The Practical Significance of Electrical
Harmonics,"Cal Lab 7, no. 3 (2000): 2326.
2. K Armstrong and T Williams, "EMC Testing Part 2Conducted
Emissions," EMC Compliance Journal, no. 34 (2001): 2232.
Available on the Internet at http://www.compliance-club.com.
3. T Williams, EMCTLA Technical Guidance Note #42Emissions
Tests on Telecom Ports as per CISPR 22 (EN 55022) and Addendum
1, (Romsey, UK: EMC Test Labs Association, 2001). Available on
the Internet at http://www.emctla.org.
Bibliography
CISPR 16-1:1993-08. "Specification for Radio Disturbance and Immunity
Measuring Apparatus and MethodsPart 1: Radio Disturbance and
Immunity Measuring Apparatus." International Electrotechnical Commission,
Geneva, 1993.
Code of Federal Regulations, 47 CFR 15.33.
Code of Federal Regulations, 47 CFR 18.101.
EN 50082-1:1997."Electromagnetic Compatibility (EMC)Generic
Immunity Standard for Residential, Commercial and Light Industrial
Environments." CENELEC, Brussels.
EN 50130-4:1995. "Alarm SystemsPart 4. Electromagnetic Compatibility
Product Family Standard: Immunity Requirements for Components of Fire,
Intruder, and Social Alarm Systems." CENELEC, Brussels.
EN 55011:1998. "Electromagnetic Compatibility (EMC)Emissions
from Industrial, Scientific and Medical (ISM) Equipment." CENELEC,
Brussels.
EN 55022:1998. "Electromagnetic Compatibility (EMC)Emissions
from Information Technology Equipment (ITE)." CENELEC, Brussels.
EN 55024:1998. "Electromagnetic Compatibility (EMC)Immunity
of Information Technology Equipment (ITE)." CENELEC, Brussels.
EN 61000-3-2:1995, 1st ed. "Electromagnetic Compatibility (EMC)Part
3: LimitsSection 2: Limits for Harmonic Current Emissions."
The European Committee for Electrotechnical Standardization (CENELEC),
Brussels.
EN 61000-3-3:1995, 1st ed. "Electromagnetic Compatibility (EMC)Part
3: LimitsSection 3: Limitation of Voltage Fluctuations and Flicker
in Low-Voltage Supply Systems." CENELEC, Brussels.
EN 61326-1:1997. "Electromagnetic Compatibility (EMC)Emissions
and Immunity for Equipment for Measurement, Control, and Laboratory
Use." CENELEC, Brussels.
GR-1089-CORE, Issue 1. "Electromagnetic Compatibility and Electrical
SafetyGeneric Criteria for Network Telecommunications Equipment."
Bell Communications Research Inc., December 1996.
IEC 60725 (1981-01), 1st ed. "Electromagnetic Compatibility (EMC)Considerations
on Reference Impedances for Use in Determining the Disturbance Characteristics
of Household Appliances and Similar Electrical Equipment." International
Electrotechnical Commission, Geneva, 1981.
IEC 61000-4-2 (1999-05), 1st ed. "Electromagnetic Compatibility
(EMC)Part 2: Testing and Measurement TechniquesElectrostatic
Discharge Immunity Test." International Electrotechnical Commission,
Geneva, 1999.
IEC 61000-4-3 (1998-11), 1st ed. "Electromagnetic Compatibility
(EMC)Part 4-3: Testing and Measurement TechniquesRadiated,
Radio-Frequency, Electromagnetic Field Immunity Test." International
Electrotechnical Commission, Geneva, 1998.
IEC 61000-4-4 (1995-01), 1st ed. "Electromagnetic Compatibility
(EMC)Part 4: Testing and Measurement TechniquesSection
4: Electrical Fast Transient/Burst Immunity Test." International Electrotechnical
Commission, Geneva, 1995.
IEC 61000-4-5 (1995-02), 1st ed. "Electromagnetic Compatibility
(EMC)Part 4: Testing and Measurement TechniquesSection
5: Surge Immunity Test." International Electrotechnical Commission,
Geneva, 1995.
IEC 61000-4-6 (1996-04), 1st ed. "Electromagnetic Compatibility
(EMC)Part 4: Testing and Measurement TechniquesSection
6: Immunity to Conducted Disturbances, Induced by Radio-Frequency
Fields." International Electrotechnical Commission, Geneva, 1996.
IEC 61000-4-8 (2001-03), 1st ed. "Electromagnetic Compatibility
(EMC)Part 4-8: Testing and Measurement TechniquesPower
Frequency Magnetic Field Immunity Test." International Electrotechnical
Commission, Geneva, 2001.
IEC 61000-4-9 (2001-03), 1st ed. "Electromagnetic Compatibility
(EMC)Part 4-9: Testing and Measurement TechniquesPulse
Magnetic Field Immunity Test." International Electrotechnical Commission,
Geneva, 2001.
IEC 61000-4-10 (2001-03), 1st ed. "Electromagnetic Compatibility
(EMC)Part 4-10: Testing and Measurement TechniquesDamped
Oscillatory Magnetic Field Immunity Test." International Electrotechnical
Commission, Geneva, 2001.
IEC 61000-4-11 (2001-03), 1st ed. "Electromagnetic Compatibility
(EMC)Part 4: Testing and Measurement TechniquesSection
11: Voltage Dips, Short Interruptions and Voltage Variations Immunity
Tests." International Electrotechnical Commission, Geneva, 2001.
Acknowledgments
The author gratefully acknowledges the assistance of Todd Robinson
(CKC Laboratories), Mike Heckrotte (PrecisionCal), and Ralph Cole
(Teradyne) in the preparation of this article.
Jerry Ramie is vice president of marketing for Compliance Systems
Corp. He is a 20-year veteran of the regulatory compliance, EMC, and
RF/microwave instrumentation businesses, with experience in EMC from
Eaton Corp., ARC Technical Resources Inc., and Compliance Systems.
He can be reached at 408-263-6486 or on the Internet at http://www.compliancesys.com.
Back
to July/August Table of Contents
|