FCC Part 68 Requirements for Connecting to
the U.S. Phone Network
ITS Intertek Testing Services (Boxborough,
MA)
Many local telephone companies sprang
up around the country after Mr. Bell's invention
of the telephone in 1877. Gradually, AT&T
purchased most of these to become the dominant
carrier and equipment provider across the U.S.
During this period AT&T developed uniform
technical rules as well as a unique terminology
("Bellspeak") for certain aspects of networks.
This terminology persists today in such terms
as "metallic," "longitudinal" and "on-hook/off-hook."
The beginnings of a breakup in this effective
monopoly began in 1956 with the Hushaphone
and 1968 Carterphone cases that broke
that monopoly, allowing other companies to interconnect
with the telephone network. To protect its network,
the telephone company supplied (and required
others to use and pay for) an interface device
known as the data-access arrangement, or DAA.
Although the DAA performed much of the network-interface
function and preserved the integrity of the
network, it had its disadvantages. First, the
user had to pay for the device, and second,
the marketing of telephone equipment became
awkward due to the necessity for the cooperation
of the Bell System.
With the growth of data communications,
the FCC saw a need for regulations to allow
direct interconnection to the telephone network
without the use of the DAA. After an involved
rulemaking process, the Commission in 1976 promulgated
the regulations now contained in Part 68 of
Title 47 of the Code of Federal Regulations.
Their purpose is "to provide for uniform standards
for the protection of the telephone network
from harms caused by connections of terminal
equipment thereto." It is important to note
that the purpose of the FCC rules is to protect
the telephone network from harm, not the consumer:
devices can be designed that will meet the requirements
of Part 68 but still not work very well. Harmonization
of FCC Part 68 rules with Canada's CS-03 took
effect April 20, 1998. The details of grandfathering
are still in question. The rules are also under
review in light of new products and technologies.
For example, 56K modems are restricted in speed
by Part 68's signal power limits. This issue
is under technical review.
What is a Telephone Network?
Conceptually, the telephone system performs
the simple task of providing a switched two-wire
connection, with enough electronics to power
a station set and amplify the audio signals
for transmission. Although much has changed
since the old days of manual and electromechanical
switchboards, their overall function has remained
constant, and, during the course of this evolution,
compatibility has always been maintained with
older station equipment. This historical legacy
of compatibility explains the nature of some
of today's interfacing specifications.
The standard two-wire telephone-set connection,
referred to as the public switched telephone
network (PSTN) or the plain old telephone service
(POTS), is not the only type of service offered
by the telephone companies. Four-wire services,
utilizing separate pairs of wires for transmitting
and receiving, afford improved fidelity; reverse
battery services allow automated PBXs to act
as localized central offices; and ground-start
and "E and M" tie trunks offer more reliable
methods of signaling than the conventional loop
system. In addition to the "public" services,
which enable the user to dial a variety of numbers,
there are also a variety of "private" point-to-point
services available in both two- and four-wire
formats. Although all of the above services
can be used by modems for audio-encoded data
transmission, the data rates available are limited
by the 4-kHz audio bandwidth provided. For higher-bandwidth
service, digital services ranging in speed up
to 1.544 Mb/sec are available, and are included
in the FCC Part 68 attachment program.
While these services vary in form, most
derive their basic operational characteristics
from the plain old telephone network.
Each telephone customer or "subscriber"
has a two-wire connection or "subscriber loop"
to the local telephone office, known as the
central office. Through a matrix-switching arrangement,
each subscriber's telephone may be connected
to any other telephone served by the central
office. Communications between offices are performed
through interoffice trunks. Channel banks are
sometimes used to compress the voice or data
signals from the subscriber loops on multiplexed
interoffice trunks.
The subscriber loops are shown in more
detail in Figure
1. The central office provides battery power,
which is fed through a current-sensing relay
coil. The dc resistance between the central
office and the customer equipment can vary from
400 to 1740 ohms and is dependent on the length
of the loop. Since the two-wire loop forms a
transmission line, the ac impedance, controlled
by the wire's spacing, is 600 ohms. Nominally,
telephones match this 600-ohm impedance over
the voice-frequency range and have a dc resistance
of less than 200 ohms when connected to the
line ("off-hook"). Power for the customer equipment
can be drawn from the central-office battery,
which will vary the voltage from 42.5 to 56.5
V. Loop current is generally in the 20 to 80
mA range.
Placing a Call
When the telephone receiver is on-hook,
the telephone draws no current from the line.
Lifting of the receiver causes a connection
to be made, allowing current to flow from the
central office. The central office detects this
off-hook state and sends a dial tone, which
in its most common form consists of a combination
of a 350-Hz and a 440-Hz tone. When the user
dials, the telephone set interrupts the loop
current, causing a current sensor (relay) at
the central office to change state. Alternating
make-and-break contacts signal the central office
that digits have been dialed, and depending
on the number, the central office connects the
subscriber loop either to an interoffice trunk
or to another subscriber. If the loop sensor
at the central office detects that the party
being called has the phone off-hook, the calling
party is sent back a busy tone (480 Hz plus
a 620 Hz tone, at 24 dBm). If the party
being called has the phone on-hook, he or she
is sent a ringing signal that makes the phone
ring (typically 20 Hz at 100 volts, superimposed
over the central office's battery voltage).
If the party being called lifts the receiver
off-hook, the central office detects the current
being drawn by the second subscriber's loop
and stops, or "trips," the ringing signal. Direct
connection is then established between the two
subscribers.
Modern technology has displaced the relays
and pulse dialers used in older telephone systems.
Dual-tone multifrequency (DTMF) telephone-address
signaling has largely replaced the old rotary-pulse
dialers, and electronic switching systems (ESSs)
have superseded the mechanical relay and crossbar
switching. Nonetheless, as far as the user is
concerned, the functioning and electrical parameters
of the system are little changed from the days
when it was built of relays and coils.
Based on these parameters, the FCC has
specified a model for simulating the central
office and the subscriber line. This simple
model simulates both the dc and the audio-frequency
characteristics of the telephone network.
Scope of Part 68 Regulations
The United States benefits from telecom
regulations that are minimal by intent. Part
68 covers only those attributes of terminal
equipment which protect the network equipment,
signals or personnel from impairment or injury.
Hearing-aid compatibility is an equal-access
provision added by the Congress. Issues of equipment
quality or functionality are left to the marketplace.
This is not the case in other jurisdictions
around the world, where detailed requirements
for interoperability are imposed upon the telecom
equipment manufacturer. As a result, the United
States has among the simplest and easiest telecom
rules anywhere. There are only a few basic tests
to be performed for the sake of Part 68 registration.
These tests may vary in implementation a bit,
however, depending upon the nature of the terminal
equipment. An excellent resource for understanding
the reasons behind the tests, and how to perform
the tests, is found in the TIA document Part
68 Rationale and Guidelines. The document reference
TSB 31B matches the Part 68 rules effective
April 20, 1998. That document serves as the
framework for what follows. It describes the
basic tests as:
1.Environmental Simulationelectric
surge voltages to the telecom connections and
the mains plug, to assure that the terminal
equipment does not fail in a way which could
tie up the network or generate damaging signals;
mechanical shock caused by shipping, to check
for circuit or component failures in transit.
2.Leakage Currentto
test if accidental failure of the power supply
or contact between mains voltage and exposed
metal surfaces could result in damaging potentials
to network equipment or personnel.
3.Hazardous Voltageto
assure that the terminal equipment does not
put voltages onto the network which exceed the
normal range of network signals.
4.Signal Power Limitationsto
verify that analog or digital signals generated
by the terminal equipment do not exceed levels
which could cause distortion, overload, or crosstalk
on the network.
5.Transverse Balancethis
measures the equality of impedances from network
connections to earth ground, to assure that
permitted differential signals ("metallic")
are not converted to common-mode signals ("longitudinal")
which can cause crosstalk in telecom cables.
6.On-Hook Impedancethis
prescribes minimum values to the dc and ac impedance
of the terminal equipment, so that it does not
interfere with the phone company's line maintenance
signals nor with the normal sequence of detecting
the on-hook state of the terminal equipment.
7.Billing Protectiontests
to assure that the phone company gets paid for
the connection or transmission of data.
8.Hearing Aid Compatibilitymeasures
the magnetic coupling from earpiece to nominal
hearing aid location, and in the future, the
acoustic gain of the telephone for the hard-of-hearing
without a hearing aid.
9.Digital Terminal Equipmentadapts
the existing tests, plus a few others, to equipment
which transmits or receives data signals ranging
from 2.4 kb/sec to 1.544 Mb/sec.
10.Miscellaneousapplies
limits to the number of automatic redial attempts,
requires identification of facsimile senders,
etc.
Part 68 specifies two tests to check
for exposure of the network to hazardous voltages.
The first is a conventional leakage test, in
which a 50- or 60-Hz voltage is applied between
the telephone connections (known as tip and
ring) and both of the following:
-
Exposed conductive surfaces.
-
Connections to equipment other than
registered telephone equipment (known as
nonregistered equipment and including such
items as computers, printers, etc.).
In order to speed testing, the Commission accepts
a simplified procedure in which, for the most
part, only the signal ground connections to
nonregistered equipment (i.e., I/O leads) have
to be considered. Since data and address lines
are at virtually the same potential as signal
ground, they may be excluded. In performing
the leakage tests, the applied voltage is increased
from 0 to 1000 V rms over a 30-second period
and maintained for an additional 60 seconds.
At no time should the current exceed 10 mA.
The second test measures the leakage current
between the primary power supply and the points
listed above, as well as that between the supply's
primary and secondary. Here the voltage is gradually
increased from 0 to 1500 V rms, and again, the
current must not exceed 10 mA.
For the leakage tests, any protective components
that will shunt current, such as varistors or
line filters, should be removed. The purpose
of the test is to demonstrate the dielectric
strength of the isolating components.
The FCC is further concerned about hazardous
voltages on the lines, defined as voltages in
excess of 70 V peak for more than one second.
To prevent such occurrences, the Commission
requires that telephone leads be physically
separated from power connections and from any
leads feeding ports that may be exposed to hazardous
voltages. Furthermore, the Commission also requires
that PC boards containing telephone interfaces
be mounted in such a way as not to be exposed
to hazardous voltages within the equipment.
To test for hazardous voltages, Part 68 requires
the network connections to be monitored with
an oscilloscope for the occurrence of a voltage
greater than 70 V peak for more than one second,
during any likely sequence of operation, handling
or repair of the terminal equipment.
The former test which applied 120 V at potentally
high current to exposed conductors has been
replaced in the 1998 rules with a ground continuity
test which is much less hazardous to the test
engineer.
It should be noted that services other than
the POTS type may impose additional requirements.
For example, because a PBX will often drive
lines to off-premises telephones, the characteristics
of the PBX DC and ringing voltage supplies are
constrained for performance and safety reasons.
Part 68 specifies signal-level maximums
for three discrete reasons. First, some telephone
lines cover such great distances that amplification
is needed. Since amplifiers have limited dynamic
range, the amount of signal placed on the line
in the voice band (2003995 Hz) must be
limited. Second, in communicating from one central
office to another, the telephone network will
use frequency- and time-multiplexing schemes,
and it is important that signals outside the
voice band be limited (up to 6 MHz) since out-of-band
signals may interact with the multiplexing to
create spurious in-band signals via frequency
aliasing. Finally, crosstalk between lines must
be controlled.
Different limits apply to voice and data
signals than to signals intended for dialing.
The latter, known as network-control signals,
may be in the form either of pulse dialing,
which is not covered by FCC regulations, or
of dual-tone multifrequency (DTMF) dialing.
The setup shown in Figure 2 can be used
for measuring voice, data, or DTMF transmissions.
The equipment under test is connected to a loop
simulator that mimics its connection to the
telephone network. Since different limits apply
in different frequency ranges, a frequency-selectable
bandpass filter is used.
 |
| Figure 2. Setup for measuring differential
(metallic) signals placed on the network.
|
In the voice-frequency range, the RMS reading,
integrated over the entire band, should be below
9 dBm (or 9 dB below 1 mW) into 600 ohms,
averaged over a 3-second period. Moving to the
4 to 12 kHz range, voice or data signals should
not be stronger than specified limits averaged
over a 100-ms period. Above 12 kHz, signal levels
are examined in every 8-kHz segment from 12
kHz to 6 MHz. In each of these 8-kHz segments,
the signal should be below the limits indicated
in the table, using the specified termination.
It is permissible to take measurements
over a bandwidth wider than 8 kHz; while the
8-kHz range is the minimum required by the rules,
a wider bandpass will speed testing.
Since 8 kHz is used for sampling by digitizing
equipment, the band from 3995 to 4005 Hz is
sensitive. For most applications, signals in
this narrow frequency band must be less than
27 dBm. For DTMF signaling, the permissible
level from 100 Hz to 4 kHz is less than 0 dBm
averaged over a 3-second period. It is measured
with the same test setup used for in-band voice
or data transmission. No limits are specified
for DTMF signals above 4 kHz.
In addition to prescribing limits for
signal levels between tip and ring, known as
metallic or differential voltages, Part 68 specifies
limits between tip/ring and earth ground, known
as longitudinal or common-mode voltages.
In the case of in-band signals (defined
for longitudinal voltages as 100 Hz to 4 kHz),
a high-pass filter is inserted in series with
the test network with frequency characteristics
as shown. The averaging period for these measurements
is 100 milliseconds.
Devices that send voice signals or music
over the network are required to be tested while
driven with a 1 kHz, 13 dBm signal.
Anything connected to the phone lines
that results in one side of the line's having
a different impedance with respect to earth
ground than the other will tend to cause differential
voltages present in the environment to be converted
to common-mode noise. This signal, which is
usually in the form of 60-cycle noise, will
show up as hum.
When unbalanced lines transmit signals
coupled in multiconductor cables, they produce
cross talk. In order to prevent this, the rules
require any equipment attached to the telephone
line to meet some minimum balance criteria.
For balance testing, an oscillator with
a 600-ohm output impedance drives the primary
of a transformer, which produces a differential
voltage on the tip and ring lines. Capacitors
are adjusted so that the voltage is nulled when
a 600-ohm resistor is placed across tip and
ring.
When the equipment under test is placed
across the tip and ring lines, some imbalance
will occur. This imbalance will cause a voltage
to be built up across the 600-ohm resistor (for
analog equipment), and this voltage can then
be compared with VM. The ratio yields the transverse
balance reading, which should exceed 60 dB below
1 kHz and 40 dB between 1 and 4 kHz. Similar
balance values apply for digital equipment up
to 1.544 Mb/sec.
On-Hook Impedance Limitations
Dc on-hook resistance is required to
be greater than 5 megohms for an applied voltage
of up to 100 V and greater than 30 kilohms for
an applied voltage of up to 200 V (see Figure
3). The telephone companies use an automated
insulation test system as part of their maintenance
routine. If the dc on-hook resistance of an
attached piece of equipment is too low, the
line is interpreted as being damaged, and repair
procedures are initiated. The dc resistance
requirement prevents false service alarms.
 |
| Figure 3. Setup for on-hook dc impedance
test. Caution: High voltage requires care.
|
 |
| Figure 4. Setup and limits for the
ac on-hook impedance test. Dividing the
applied voltage by the ac current yields
the impedance. In a second test, a 100-kilohm
resistor is connected to tip or ring; the
voltage observed on the oscilloscope should
fall by more than a factor of 2. |
Since the central office also has to make the
phone ring, the rules specify a minimum ac on-hook
impedance for the ringer as well. During this
test (Figure 4), a ringing signal is applied
to the equipment under test.
Under the 1998 rules either of only two
ringer frequencies A (20, 30 Hz) and B (1568
Hz) are used. A minimum impedance must be met,
depending on the ringer and frequency of 1400
ohms at 20 Hz and 1000 ohms at 30 Hz for ringer
A, or 1600 ohms at 1568 Hz for ringer
B.
As part of the on-hook impedance limitations,
the FCC specifies two additional tests. First,
during the ringing test, dc current is also
measured and must not exceed 3 mA. Second, the
Commission requires a minimum "longitudinal"
impedance of 100 kilohms from each tip and ring
to ground. A convenient way of measuring this
is shown in Figure 5. A 100-kilohm resistor
from either tip or ring to earth ground is attached
while the ringing test is performed; if the
voltages measured from tip and ring to earth
fall by more than a factor of 2, then the longitudinal
impedance of the equipment under test is greater
than the specified 100-kilohm limit.
 |
| Figure 5. Separating transmit from
receive: the transmitted signal is fed simultaneously
to the interface through a resistor and
to a second inverting amplifier, causing
cancellation. |
These on-hook impedance tests are designed
to protect the network from excessive current
flow while on-hook. However, if several devices
are connected to the same phone line, excessive
current may still be drawn. To prevent this,
a system known as ringer equivalence number
(REN) is used. As a standard, the amount of
current drawn by an old telephone (known as
the 500 set) is assigned a REN of 1. A device
that draws twice as much current has a ringer
equivalence of 2, and so on. The ringer equivalences
of parallel devices add, with the maximum ringer
equivalence (i.e., the sum of all attached devices)
for any installation being 5.
The REN is followed by a letter corresponding
to the type of ring signal applied during testing.
For example, if the highest REN calculated was
.8, and the device was tested as a B-type ringer,
the REN would be 0.8B.
Although Part 68 specifications are adequate
to protect the network, they do not fully define
all characteristics needed for optimal device
design. For example, device dc off-hook resistance,
which is not specified by Part 68, should be
approximately 200 ohms, while off-hook ac impedance
should match the network's impedance of 600
ohms. Additional information on standard practice
may be found in TIA and ANSI standards and in
Bellcore publications.
Telephone companies are understandably
anxious that customer premise equipment should
not upset their ability to bill for service.
To this end, four rules have been included in
Part 68 under the heading "Billing Protection."
1.For data equipment (that is,
telephone devices that send data on the network),
the rules stipulate that no usable data should
be sent or accepted for at least two seconds
after equipment answering a call seizes the
telephone line. A two-second delay must therefore
be built into the hardware or device firmware
for equipment that automatically answers the
line. This requirement does not apply to signals
sent down the line for establishing synchronization
or mode of operation.
2.Billing-protection calls for
signals in the 200 to 3995Hz band should
be below 55 dBm when on-hook. This measurement
may use the same apparatus shown in Figure 2.
3.Within the first five seconds
after an incoming call is answered, a device
must either draw at least as much current as
a 200-ohm resistor would or exhibit a current
"overshoot" of less than 25%. This requirement
prevents a device from seizing the phone line
and taking advantage of the differing current
levels used for seizure and billing to receive
a free call.
4.Energy in the band between 2450
and 2750 Hz must be at least equal to that in
the band from 800 to 2450 Hz at all times. Compliance
will avoid excessive energy at 2600 Hz, the
in-band signaling sometimes used between central
offices. The setup for making this measurement
is shown in Figure 2.
The device is first subjected to drop
tests. Unpackaged drop tests on equipment that
is not usually carried by the customer are performed
from heights of 6 inches on each resting face
and 3 inches on all other faces and corners;
equipment that is normally carried is dropped
from a height of 30 inches in a random fashion,
except for equipment used at head height, which
is subject to 18 random drops from a height
of 5 feet. All of these drop tests employ a
concrete surface covered with 1/8
inch of asphalt tile.
If the equipment survives these tests,
it is subjected to two voltage surges that simulate
lightning and other transients occurring on
power or telephone lines. There are two types
of surge, A and B, to be applied. In between
them, the terminal equipment must be checked
for compliance and on-hook/off-hook functionality
of the interface.The new Type B surge is a 9
x 720 ms pulse, 1000 V metallic and 1500 V longitudinal.
One pulse of each polarity is applied. Then
the Type A surge is applied (this is the pulse
specified in the 1997 rules). Two 800-V surges
are applied between tip and ring, with a 10-µs
maximum front time and a 560-µs minimum
decay time (to half crest), one of each polarity.
Fifteen-hundred-volt longitudinal surges of
each polarity are required between the telephone-line
connections and earth ground, on each of the
telephone lines individually and with both lines
tied together. The maximum front and minimum
fall times here are 10 and 160 µs, respectively.
A last surge test is applied between the phase
and the neutral wires of the ac line if the
device uses ac power. Three surges of each polarity
(six in all) are applied at a level of 2500
V, each having a 2-µs maximum front time
and a 10-µs minimum decay time.
After environmental simulation, all of
the tests described above (leakage, hazardous
voltage, signal power, balance, on-hook impedance,
and billing protection) are performed again.
Any variations between readings must be explained
in the registration application. Although devices
may be damaged, they must still meet the "non-harm"
requirement: for example, it is acceptable for
a piece of equipment to fail after the Type
A surge in the permanently on-hook state, but
a unit that is permanently off-hook after this
surge may not be registered.
Digital Terminal Equipment
Data rates from 2.4 Kb/sec ("subrate")
to 1.544 Mb/sec (T-1 and ISDN) are regulated
under Part 68 by applying tests very similar
to voice band terminal equipment: signal power,
transverse balance and environmental requirements
apply. In addition, there are tests specific
to data devices: pulse frequency, waveform templates,
and signaling duration. Within the network,
these digital signals are sometimes decoded
and then re-digitized; therefore, the "encoded
analog content" must be analyzed for the same
parameters as for an analog phone: network signal
levels (comparable to DTMF), non-network signals,
and on-hook signal power.
Separating Transmit from Receive
From its beginnings, the telephone system
has always been a two-wire full-duplex system,
meaning that a single pair of wires carries
signals in both directions. When data are transmitted,
collisions will result that a computer cannot
resolvehence, the need for circuits known
as hybrids (Figure 5), which cause cancellation
of the transmitted signal and leave the telephone
device free to receive signals coming down the
telephone line. In Figure 5, the transmitting
signal is fed to a follower, which drives resistor
RH and the telephone-interface transformer.
Since the telephone line is nominally 600 ohms,
the transmitted signal is divided by 2 through
this process. The signal VA is therefore the
voltage received down the telephone line (VR)
plus one half the transmitted voltage (VT).
This combined signal is fed to a noninverting
gain-of-2 amplifier, which simultaneously subtracts
VT, causing cancellation of the transmit signal.
Note, however, that the ability of the circuit
to separate transmit from receive depends on
the impedance of the telephone line. If it is
exactly 600 ohms, signal rejection may be as
high as 40 dB (factor of 100), though in most
applications, loop rejection greater than 20
dB cannot be expected.
Up to this point, we have focused on
a two-wire connection to the public switched
telephone network. However, there are many other
kinds of connections provided by local operating
companies and regulated by the FCC.
The conventional two-wire circuit is
one type of public switched line. Such lines
allow calls to any other public telephone subscriber.
There are also private lines, which usually
implement a dedicated connection.
Public switched lines come in several
basic forms. Loop-start lines are the kind we
have explored: to start the process, the user
draws loop current from the central office.
There is also the more robust ground-start system,
in which the subscriber initiates a call via
an earth-grounding ring and is alerted to an
incoming call either by the sight of earth ground
in tip or by a conventional ring signal. Often
used in PBXs, such systems prevent collisions
between incoming and outgoing calls by speeding
the recognition of alerting (ringing) signals.
There are also direct inward dial (DID) lines,
which reverse the roles of the customer and
the central office. Here the central office
does the dialing, and the customer's PBX receives
the number of the person that the central office
wants to ring. The PBX then connects the central
office line to that individual's phone. This
bypasses the switchboard attendant through the
use of "direct dial" numbers.
Private lines also come in other flavors.
In tie trunks, used to tie two PBXs together,
the reliability of dialing and ringing is improved
through the use of a separate "E and M" pair
dedicated to alerting (ringing) and signaling.
"Standard" telephone lines are available
in private-line form as well. Such a line is
known as a ringdown tie trunk. If only a short
connection is needed, one possible choice is
a metallic channela pair of wires strung
by the telephone company from point to point.
Alternatively, a PBX can connect to a station
in a remote location by using an off-premise
station (OPS) line.
Finally, users of local-area networks
may want to consider the telco's own offering,
the local-area data channel (LADC).
To protect these various telephone facilities,
Part 68 requires further tests in addition to
those specified for two-wire loop-start lines.
Such treatments, though similar to those discussed
above, are beyond the scope of this article.
Other Requirements in Part 68
Notable changes that affect manufacturers
include:
-
RF immunity requirements: recently
the FCC has become concerned about the number
of reports it has received of radio interference
to telephones. This concern is driven by
complaints from telephone companies that
they spend millions on servicing such problems
but can do little about them because they
neither make nor own the affected equipment.
At the FCC's behest, the TIA has published
an RF immunity standard (TIA 631) aimed
specifically at telephone station sets.
The FCC has made it clear that some form
of RF immunity is needed, and that it will
initiate a rulemaking if industry quality
standards do not improve. The imposition
of RF immunity standards would be a first
for the FCC.
-
Premises wiring: The rules
on premises wiring have been liberalized
to afford customers increased access. The
carrier's wiring can now be cut out or spliced,
and the wiring for small systems using up
to four lines freely installed, without
further inspection. The point of demarcation
between customer- and telco-owned wiring
is moved as close to the property boundary
as possible, generally within 12 inches.
-
PBX billing policy: PBX manufacturers
have to observe strict call-handling guidelines
on DID lines. The telephone companies, which
depend on the PBX to let them know when
a successful call is in progress by reversing
the polarity of the DID line, complained
that this was not always done properly and
was costing them hundreds of millions of
dollars annually in lost billings. Section
68.314 of Part 68 makes proper DID supervision
a prerequisite for FCC registration.
-
Hearing-aid compatibility (HAC)
volume control: Soon, all telephones other
than mobile phones and private radio phones
must have receive-volume controls capable
of a minimum of 12 dB of gain relative to
the ROLR (Receive Objective Loudness Rating).
This 12-dB gain adjustment will allow the
user to increase the receive volume and
at the same time increase the magnetic coupling
field of the handset to the hearing aid.
The ROLR measurements and associated gain
measurements are to be conducted in accordance
with the processes defined in ANSI/EIA-470-A-1987
for analog equipment or ANSI/EIA/TIA-579-1991
for digital equipment. Telephones using
loop signaling must also conform with the
upper and lower ROLR limits specified in
ANSI/EIA-470-A-1987 while set in normal
receive-volume mode. The receive-volume
adjustment may not exceed a maximum of 18
dB of gain unless the telephone automatically
resets to normal when returned to an on-hook
state. Many manufacturers are currently
investigating ways to meet the 12-dB gain
requirement so they can be in compliance
prior to the effective date of the specification.
The phase-in dates are given in Table
I.
-
ISDN (Integrated Services Digital
Network): As of November 13, 1996, all customer-premises
ISDN equipment must be registered under
Part 68 rules and specifications. All ISDN
equipment connected to the network prior
to that date should have been registered
under the grandfather rule before December
13, 1997. The current regulation addresses
both Primary Rate ISDN and Basic Rate ISDN
equipment, assigning facility-interface
codes to both types. The regulation also
subdivides these two interfaces into classifications
relating to their placement in the network,
coded as DD, DE, and XD. These codeswhich
are the same as those used in the registration
of Subrate and T1 digital equipmentdefine
the level of protection and isolation of
the registered device from the telephone
network. Evaluation requirements defined
in the regulation for each individual interface
type include the environmental simulation.
-
PSDS (Public Switched Digital Service):
The current issue of CFR 47, Part 68, also
regulates equipment intended for connection
to Public Switched Digital Services (PSDS),
commonly referred to in the industry as
"Switched 56." This includes all three types
of PSDS interfaces in both two-wire and
four-wire configurations. These interfaces
are categorized under the same classification
codes (DD, DE and XD) as other digital equipment
covered by the Part 68 regulation, and were
allowed in under the same grandfathering
policy as the ISDN interface. The electrical
and environmental evaluation requirements
are specified in the current Part 68 regulation
and are addressed in EIA/TIA TSB31B.
-
CTI (Computer Telephony Integration):
Registration of host-dependent and host-independent
modules is permitted. Systems may be configured
from registered components, without the
need to register the overall system. Two
categories of modules have been created:
CN, providing an analog or digital network
interface; and CE, generating signals, gain
or billing protection parameters.
Although Part 68 appears to be a daunting
document, it covers for the most part only harms
to the network. Also, Part 68 contains the regulatory
requirements for all terminal equipment: analog,
digital, private-line, PBX, voice, and nonvoice.
The telecom rules for many other countries are
much more comprehensiveand, in many cases,
are divided into separate standards for each
type of terminal device. This makes them less
accessible as well as more difficult to meet.
The relative simplicity of the U.S. telecom
connection requirements no doubt contributes
to a vibrant domestic marketplace for telecom
products and technologies.